EtherNet/IP interface
71
AMS 358
i
Leuze electronic
9.7.3.3
Password
Attribute 3
The attribute specifies the password. The password protection attribute (attribute 2) must
be active. Value range of the password: 0000 - 9999.
The master password
2301
can be used to activate parameter enabling via the display/
panel.
9.7.3.4
Illumination
This attribute is used to set whether the display illumination is to be switched off 10 minutes
after the last button operation or whether the illumination is always to be on.
0 = display illumination off 10 minutes after the last button operation
1 = display illumination always on
9.7.3.5
Contrast
When exposed to extreme ambient temperatures, the display contrast may change. This
attribute adjusts the display illumination.
9.7.3.6
Extended heating control
This attribute is used to activate extended heating control.
The extended heating control range of the internal device heating may prevent condensation
from forming on the optics of the AMS 358
i
. The internal heating of the AMS 358
i
is switched
on at higher ambient temperatures (30 °C) if the parameter is set.
In the event of very large and fast fluctuations in temperature and humidity, the power of
the internal heating may not be sufficient to prevent condensation.
9.7.4
Class 101 Selection assembly
Object class 101 = 65
H
Service:
• Get_Attribute_Single
• Set_Attribute_Single
Value
Contrast
0
Weak
1
Medium
2
Strong
On
Off
0 = switch-on / switch-off temperature of internal heating:
10 °C (50 °F)
15 °C (59 °F)
1 = switch-on / switch-off temperature of internal heating:
30 °C (86 °F)
35 °C (95 °F)
Path
Designation
Size
in bit
Data type
Default
(dec)
Min
(dec)
Max
(dec)
Access
Cl.
Inst.
Attr.
101
1
1
Input assembly ID
8
BYTE
1
see below
Set
2
Output assembly ID
8
BYTE
120
see below
3
Config assembly Id
8
BYTE
190
see below