RUN operating mode - normal operation

The RUN operating mode is the standard operating mode in which the sensor detects objects; it signals this according 
to the set functions. If the selector switch for the operating mode is in the 

RUN

 position, no changes can be made on 

the device. This setting is thus suitable for protection against unintended operation and changes to device settings.

PRG operating mode - sensor adjustment

The LV463 can be adjusted to meet customer requirements with a simple menu-driven system. 
To do this, set the 

selector switch

 for the 

operating mode

 to position 

PRG

.

The menu consists of 13 successive subfunctions. Rock to right or left to freely navigate through the subfunctions.

Selector switch 

Operating mode

RUN

:

Normal  mode  -  no settings possible.

ADJ

:

Press rocker push button: the set teach is executed.
Rock to left - right: change the switching threshold, left = 

+

 and right = 

-

.

PRG

:

Menu-driven device setting via display and rocker push button.

Selector switch

Switching output

LO

:

Switching output 

light switching

If throughbeam fiber optics are installed, the switching output is active when the 
light path is free; if a scanning system is installed, the switching output is active 
when an object is detected. The status LED illuminates when the switching output 
is active.

DO

:

Switching output 

dark switching

The switching behavior is the inversion of the 

light switching

 setting.

Rocker push button 

- Set switching threshold
- Navigation in menu

The 

rocker

 

push

 button can be rocked 

to the right

 and 

to the left

 and 

pressed

 

in the middle position.

Rock 

+, -

:

In  the 

ADJ

 operating mode, the switching threshold can be increased (

+

) or 

decreased (

-

) by rocking. In the 

PRG

 operating mode, rock to navigate in the 

menu.

Button:

Press the rocker push button in the middle position to accept a setting made in 
the 

PRG

 operating mode.

Indicator 

Signal strength

In the 

RUN

 and 

ADJ

 operating modes, the display shows the current signal value. 

In the 

PRG

 operating mode, information on menu navigation appears on the 

display.

Indicator 

Switching threshold

In the 

RUN

 and 

ADJ

 operating modes, the display shows the currently set 

switching threshold. In the 

PRG

 operating mode, information on menu navigation 

appears on the display.

Status LED (yellow)

Switching output state

LED 

ON

Switching output active.

LED 

OFF

Switching output inactive.

 

OFF

 

dLY 

FctY

dEF

ZEro

 

OFSt 

 

Func

SEL 

InP

SEL

dISP

 

rEAd 

On

ISho

 

OFF

ISho

On

dLY

GAIn

SEL 

Verstärkung 

auswählen 

GAIn

SEL 

tch

 

SEL

Teachart 

auswählen 

tch

 

SEL

rESP

 

SPd 

Auto

 

thr 

Antwortzeit 

auswählen 

rESP

 

SPd 

Select 

response time

Select 

gain

Select 

teach mode

Master-slave 

assignment

Offset 

calibration

Factory setting

Threshold 

tracking

Switch-off delay

Passing contact 

OFF

Start-up delay

Passing contact 

ON

Turn 

read direction 

multi funct 

input

LV463B

Summary of Contents for 50126587

Page 1: ... diode for operation and switching output Connection via M8 connector cable or cable with M12 connector up to 1700mm up to 450mm 10 30 V DC 50 kHz Accessories available separately Plastic fiber optics KF KFX Glass fiber optics GF Ready made cables KB Mounting device BTU LV463 IEC 60947 IEC 60947 Dimensioned drawing A Clamping lever for fiber optic cable unlock in direction of arrow B Connection fo...

Page 2: ...ironmental data Ambient temp operation storage 10 C 55 C 20 C 85 C Protective circuit 4 4 2 polarity reversal protection 3 short circuit protection for all outputs 2 3 Protection class IP 50 NEMA 1 Standards applied EN 60947 5 2 Certifications UL 508 C22 2 No 14 13 3 5 5 These proximity switches shall be used with UL Listed Cable assemblies rated 30V 0 24A min in the field installation or equivale...

Page 3: ... Close the transparent protective cover Controls and indicators DIN rail TS 35 35mm x 7 5mm DIN rail TS 35 35mm x 7 5mm Spring mounted DIN rail mount The amplifier is mounted as shown on a TS 35 DIN rail while disconnected from voltage Alternatively the amplifier can also be mounted without a DIN rail using the mounting accessory and M3 screws Slide switch switching output light LO dark DO switchi...

Page 4: ...tput is active DO Switching output dark switching The switching behavior is the inversion of the light switching setting Rocker push button Set switching threshold Navigation in menu The rocker push button can be rocked to the right and to the left and pressed in the middle position Rock In the ADJ operating mode the switching threshold can be increased or decreased by rocking In the PRG operating...

Page 5: ... threshold 2 point teach static the switching threshold is calculated at approxima tely midway between two signal values e g teach to two different objects or teach to the same object at two different distances from the probe Exa mple signal value 1 100digits signal value 2 400digits Switching threshold 280digits Actuate the rocker push button to or to make fine adjustments to the threshold Dynami...

Page 6: ...ter settings mA n number Defines that this unit operates as master and a total of n sensors were wired in parallel Value range n 2 6 Example mA 4 means Unit is the master a total of four sensors are connected to one another via the multi funct multifunction input Slave settings SL n number Defines that this unit operates as a slave and has the individual address n Value range for address n 1 5 Exa...

Page 7: ... t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT Switching threshold Time t Time t Signal OUT rising edge falling edge active state of the switching output se...

Page 8: ...y In this case the signal value may be too small and cannot be accepted as a teach value Table with minimum teach values as a function of the setting Check object and or placement and repeat event 2nd appears on the green display the red display shows the current signal value Place object 2 or object at distance 2 and press the ro cker push button within one minute The second te ach value is accep...

Page 9: ...5ms slaves with the same address operate synchronously Variant 2 Synchronous operation by means of an external activation signal at multi funct input pin 2 ws WH Setting for subfunction Function InP SEL multi funct input SYnc PLc activation input Slaves Slaves Master All multi funct multifunction inputs pin 2 ws WH are connected in parallel For settings see subfunctions Maximum 6 minimum 2 units 1...

Page 10: ...with the falling edge 1 Static 1 point teach The current signal value is accepted as the teach value with the falling edge 2 Static 2 point teach The current signal value is accepted as teach value 1 with the falling edge 3 Dynamic teach The sensor begins scanning the signal values with the falling edge Notice The sensor has no timeout in teach mode until the next rising edge The teach event is co...

Reviews: