background image

SIO-V.680 EN

box content

installation

product overview

charger set-up

 

@

: www.lestar.pl, [email protected]

contact:

charger

model

serial

number

invoice

number

seller’s stamp 

and signature 

1. stack mount                                                                                     2.  wall mount

1. 1 pcs. set-up                                                                         

2. up to 4 units parallel set-up

safety warnings

1. utility (L1) 2. UPS DC port connector (L2) to ZMA (externall battery) socket 3. connection socket 4. ventilation holes

  

1

  

2

  

1

  

2

         

 CHG300W  charger                                SIO +warranty                                         utility cable                                port connector to ZMA

                   mounting brackets                            mounting bracket                            mounting screws  

20 cm

20 cm

20 cm

humidity 30%~90%

L1 x 1 pcs        

L2 x 1 pcs        

A1 x 2 pcs

A2 x 1 pcs

S1 x 5 pcs        S2 x 4 pcs

2. UPS DC port connector

1. utility        

            utility                                          utility                                        utility                                         utility

UPS DC port connector

   INSTALLATION NOTES:

1. for parallel set-up
    * 24V may parallel to max. 4 chargers to 1200W (for 4 pcs. the max. input current: 8,8A, max.  charging current: 50,0A)
    * 48V may parallel to max. 4 chargers to 1200W (for 4 pcs. the max. input current: 8,8A, max.  charging current: 25,0A)
    * 72V may parallel to max. 4 chargers to 1200W (for 4 pcs. the max. input current: 8,8A, max.  charging current: 16,8A)
2.  for 2 charges connected in parallel, please select 16A line material for charger line in parallel of input and output
3.  for 3 or 4 charges connected in parallel, please select 14A line material for charger line in parallel of input and output
4. in order to connect port connector L2 to ZMA (externall battery) socket you should separate port connector blocks. please place 
    thin screwdriver into the hole between blocks and gently push them apart. please make sure  that port connector is locked tightly 
    into socket to avoid independence between male and female connector.

EN

CHG300 - external battery charger

Lestar external chager CHG300W-24Vdc output with 12.5A charging current max.

Lestar external chager CHG300W-48Vdc output with 6.25A charging current max.

Lestar external chager CHG300W-72Vdc output with 4.20 A charging current max.

SIO - 

quick start guide

        

This Quick Guide is for basic information only with reference to few safety instructions and 

external charger functions. Before use and installation you should read full manual (PIO) for conected 

UPS and ZMA (external battery bank cabinet) located on website: www.lestar.pl, especially safety 
warnings, which fully complay to this device. Installation should be performed by qualified 
personel only!

warranty card