Alfa
23
hot air gas-
fi
red air heaters
In support of engineering, installation, servicing, and maintenance
52.10.03.2017.eng
m
in.500
mm
m
in.300
mm
m
in.500
mm
Flue extraction
Air inlet
102C
108CH
Flue extraction
Air inlet
509CK
518C
102C
Flue extraction
Air inlet
105CV
105CF
518CS
108CH
890CH
Flue extraction
Air inlet
518CS
108CH 890CH
102C
102C
102C
Flue extraction
Air inlet
110FHC
Flue extraction
Air inlet
509CK
102C
105CF
125MVC
m
in.1000
mm
m
in.1000
mm
m
in.500
mm
m
in.500
mm
m
in.300
mm
Air suction in interior,
fl
ue extraction through facade. The outlet opening must
be at least 500 away from facade and in
fl
ammable objects.
Air suction in interior,
fl
ue extraction through facade. The outlet opening must
be at least 500 away from facade and in
fl
ammable objects. Flue extraction duct
must be longer by at least 300 mm and from suction inlet to avoid spurious
fl
ue
suction into interior. Connection to the hot air unit is via a coaxial inlet, such as for
installation of the unit on the pivoted bracket.
Air suction and
fl
ue extraction through facade. Minimum distance of the
fl
ue
extraction outlet from facade and in
fl
ammable objects is 500 m. Flue extraction
duct must be longer by at least 300 mm and from suction inlet to avoid spurious
fl
ue suction into interior.
Air suction and
fl
ue extraction through roof. The outlet must be at least 1,000
mm away from roof surface and in
fl
ammable objects. Connection to the hot air
unit is via a coaxial inlet, such as for installation of the unit on the pivoted bracket.
Air suction and
fl
ue extraction through facade. The outlet opening must be at
least 500 mm away from facade and in
fl
ammable objects.
Air suction in interior,
fl
ue extraction through roof. The outlet opening must be
at least 1,000 mm away from roof and in
fl
ammable objects
Example - fume extraction - coaxial
Example: single-pipe fume extraction