Electric Power Generation
Model
S/N
Enclosure
Th. Class
Weight
AVR
Date
Protection
Altitude
PF
Excitation
Freq.
Speed
Voltage
Phase
V
min
-1
Hz
kVA
kW
A
kVA
kW
A
Connection
Cont.
BR
40°C
Std by.
PR
27°C
Made in Europe by Leroy-Somer
IEC 60034 - 1& 5
ISO 8528 - 3
NEMA MG1 - 32 & 33
MOTEURS LEROY-SOMER
2 BD MARCELLIN LEROY - 16000 ANGOULÊME - FRANCE
Excitation
415 v / 40°C
DE bearing
NDE bearing
No Load
Full Load
www.leroy-somer.com
LSA
000-1-148 a
Scan the code or go to
GEN.LS1.DO
to check product data
12345678910
LSA
Installation and maintenance
LSA 42.3
Low Voltage Alternator - 4 pole
4803 en -
1 - RECEIPT
1.1 - Standards and safety
measures
Our alternators comply with most
international standards.
See the EC Declaration of Incorporation on
the last page.
1.2 - Inspection
On receipt of your alternator, check that it
has not suffered any damage in transit. If
there are obvious signs of knocks, contact
the transporter (you may be able to claim
on their insurance) and after a visual
check, turn the machine by hand to detect
any malfunction.
1.3 - Identification
The alternator is identified by means of a
nameplate fixed on the machine (see
drawing).
Make sure that the nameplate on the
machine conforms to your order.
So that you can identify your alternator
quickly and accurately, we suggest you fill in
its specifications on the nameplate below.
1.4 - Storage
Prior to commissioning, machines should
be stored:
- away from humidity (< 90%); after a long
period of storage, check the machine
insulation. To prevent the bearings from
becoming marked, do not store in an
environment with significant vibration
.
1.5 - Application
This alternator is mainly designed to
produce electricity in the context of
applications involving the use of
generators.
1.6 - Usage restrictions
Use of the machine is restricted to operating
conditions (environment, speed, voltage,
power, etc) compatible with the characteri-
stics indicated on the nameplate.