- 19 -

6.1 How to replace INPUT fuse for NB7525 and NB1K25

6.1.1 Turn off the UPS.

6.1.2 Use screwdriver to release input fuse.

6.1.3 Replace blown fuse with the new one. (Replace with the same type and same

rating fuse only.)

6.1.4 Assemble the fuse holder to the same position. Then, turn on the UPS.

TROUBLE SHOOTING

If the UPS does not operate properly and you cannot solve the problems using this

troubleshooting information in this user's guide, please contact your LEONICS local

distributor, LEONICS Service Center, send e-mail to [email protected] or visit

www.leonics.com.

Replace input fuse (10 A) following section 6.1

Turn on BATTERY circuit breaker following section

6.3

Replace input fuse (15 A) following section 6.1

Turn on BATTERYcircuit breaker following section

6.3

Turn on INPUT circuit breaker  following section

6.2

Turn on BATTERY circuit breaker following section

6.3

Turn on INPUT circuit breaker  following section

6.2

Turn on BATTERY circuit breaker following section

6.3

Check BREAKER FUSE inside the fuse holder of

BATTERY unit whether it is blown (Only NBP0811

and NBP1011). If it is  blown, replace the new fuse

with same size and same rating as the original one.

NBP 7525

NB 1K25

NB 2K25

NBP 3K25

NBP 5K25

NBP 6K25

NBP 0811

NBP 1011

No indicator displays at the panel when the

UPS is turned on.

UPS does not supply backup power when

power fails.

No indicator displays at the panel when the

UPS is turned on.

UPS does not supply backup power when

power fails.

No indicator display at the panel when the

UPS is turned on.

UPS does not supply backup power when

power fails.

No indicator displays at the panel when the

UPS is turned on.

UPS does not supply backup power when

power fails.

MODEL

PROBLEM

SOLUTION

- 20 -

6.2 How to turn on INPUT circuit breaker for NB2K25,  NBP 3K25,  NBP 5K25

NBP 6K25,  NBP 0811 and NBP 1011

6.2.1 Turn off the UPS by pressing the POWER  button  at the front panel.

6.2.2 Turn on the INPUT circuit breaker

6.2.3 Turn on the UPS by pressing the POWER button at the front panel.

6.3 How to turn on BATTERY circuit breaker

6.3.1 Turn off the UPS by pressing the POWER  button  at the front panel.

6.3.2 Turn on the INPUT circuit breaker.

6.3.3 Turn on the UPS by pressing the POWER button at the front panel and wait

until INVERTER indicator is lit.

6.3.4 Turn on the BATTERY circuit breaker.

Caution:

Turn on the UPS by pressing the POWER button  first every time.

Do not turn on the BATTERY BREAKER when the UPS is still operating

because it may damage.

MAINTENANCE

7.1 LEONICS UPS does not need any special maintenance. Just only keep it away from

dust and humidity.  Anyway, if any of following items occurred, please contact us

or our nearest service center.

7.1.1 Part of the cable is cut, broken or damaged.

7.1.2 The inside is wet with any kind of liquids.

7.1.3 The metal cabinet is broken.

7.1.4 The UPS is dropped, fallen, crashed or hit.

7.1.5 User notices abnormal conditions under normal use.

7.2 Under normal operation and continuous use, expected life time of ventilation fan is

approximately 20,000 hours.

7.3 Even though the backup batteries are maintenance free type, user still need to check

them every year to make sure that they are at good condition by  following the

 procedure  on the next page,

Summary of Contents for NB 1K25

Page 1: ...NBP series NB series TRUE ON LINE DOUBLE CONVERSION UPS LEN MAN UPS 068 Rev 3 00 2008 www leonics com e mail global_business leonics com U S E R S G U I D E ...

Page 2: ...CONTENT SAFETY INSTRUCTIONS 1 INTRODUCTION 3 FRONT AND REAR PANEL 6 INSTALLATION 14 OPERATION 16 TROUBLESHOOTING 19 MAINTENANCE 20 ...

Page 3: ... plugging and unplugging the load in order to avoid electric shock from touching two surfaces with different potential 1 1 8 It is recommended to connect the UPS to a three wire AC source two poles plus ground which connects to a protected circuit such as employs a fuse or automatic circuit breaker 1 2 CAUTION Safety guide for installation and operation 1 2 1 Install the UPS in dry location with g...

Page 4: ... to avoid electric shock 1 3 5 Replace batteries with the same type and rating and follow the proper battery replacement procedure Vocabulary Load Any equipment which is plugged into the UPS and gets power from the UPS such as a computer printer fax machine or modem UPS NB Series and NBP series UPS VA The unit of UPS power rating showing its capacity 2 2 1 When utility power and loads are normal A...

Page 5: ...on and turn off the UPS 3 1 2 FUNC button The button to mute alarm sound or turn on the LCD s back light The back light will turn off automatically in 10 seconds after release this button 3 1 3 LINE indicator The Indicates when utility line normally 3 1 4 RECTIFIER indicator The indicator is displayed when utility line normally It supplies power to the UPS in rectifier section and supplies power t...

Page 6: ...al port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 2 14 BATTERY TERMINAL for NBP0811 and NBP1011 The teminal for connecting to extension battery unit 3 1 13 LCD DISPLAY The screen to displays Input voltage Vin Output voltage Vout Battery Level B and Load level LD as shown in the picture below Note The valu...

Page 7: ...reaker OPTION Thecomponenttoswitchthepower source of loads to utility power when maintenance 3 1 18 SNMP AGENT OPTION The additional port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 1 19 NO LOAD SHUT DOWN SWITCH The switch to enable automatic shutdown when there is no load and power fails No load means the ...

Page 8: ... 11 3 2 6 3 2 1 3 2 12 3 2 9 3 2 8 3 2 7 3 2 13 3 2 10 3 2 11 12 ...

Page 9: ...loads 3 2 11 GROUND The terminal for connecting to ground system 3 2 12 MAINTENANCE BYPASS SWITCH option Turn this switch to position B when UPS is under maintenance 14 INSTALLATION Model Input cable mm2 Output cable mm2 Earth cable mm2 Battery cable mm2 NB2K25 2 5 4 1 5 2 5 2 5 4 NBP 3K25 4 2 5 2 5 4 NBP 5K25 6 4 4 NBP 6K25 6 6 6 NBP 0811 10 6 10 6 6 NBP 1011 16 16 10 6 10 4 1 Connect the RS 232 ...

Page 10: ...rn on INPUT circuit breaker 5 1 2 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 2 3 Turn on BATTERY circuit breaker 5 1 3 Model NBP 0811 and NBP 1011 5 1 3 1 Turn on INPUT circuit breaker 5 1 3 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 3 3 Turn on BATTERY circuit breaker 5 1 3 4 Turn on OUTPUT circuit breaker Note When the UPS is out of order turn on...

Page 11: ...ch as when user turns on computers When the loads consume power less than 125 for 10 seconds UPS switches back to normal operation mode 5 3 4 If you connect loads to UPS more than 100 OVERLOAD indicator is lit we recommend you to unplug some of them until load is less than 100 to let loads get high quality power from UPS and backup power from battery Note LEONICS suggests that for highest reliabil...

Page 12: ... UPS is turned on UPS does not supply backup power when power fails No indicator displays at the panel when the UPS is turned on UPS does not supply backup power when power fails MODEL PROBLEM SOLUTION 20 6 2 How to turn on INPUT circuit breaker for NB2K25 NBP 3K25 NBP 5K25 NBP 6K25 NBP 0811 and NBP 1011 6 2 1 Turn off the UPS by pressing the POWER button at the front panel 6 2 2 Turn on the INPUT...

Page 13: ...n user wants to use the UPS plug the INPUT CABLE to wall outlet utility line Turn on POWER button and wait until the ventilation fan blows Then turn on BATTERY circuit breaker 7 4 2 Model NB 2K25 NBP 3K25 NBP 5K25 and NBP 6K25 7 4 2 1 Turn off the UPS by pressing the POWER button at the front panel 7 4 2 2 Turn off the BATTERY circuit breaker 7 4 2 3 Turn off the INPUT circuit breaker 7 4 2 4 When...