Leonard XL-150-2P Installation Adjustment Service Download Page 2

2

SETUP INSTRUCTIONS

METHOD W SET-UP INSTRUCTIONS

Before any attempt is made to adjust this system, be sure the temperature of the hot water

at the source is properly set and maintained.

1.

Shut off circulator, turn ball valve #2 off.

2.

Open enough fixtures to flow a minimum of 6 GPM.

3.

Set mixing valve #1 to the desired temperature, (note Warning Tag attached to the
pointer of the valve).

4.

Open ball valve #2 and close ball valve #1.

5.

Set mixing valve #2 to the desired temperature, (note Warning Tag attached to the
pointer of the valve).

6.

Open all ball valves.

7.

Shut off all fixtures. Note: At this point, be sure NO water is being drawn through any
fixture until the temperature in the recirculated line has been set.

8.

Fully open the circuit setter and start the circulator. Make sure no water is being drawn.

9.

Observe the temperature until it stabilizes.

10. Close the circuit setter slightly if the temperature is to hot, and again let the temperature

stabilize. Repeat until the desired recirculated temperature is set.

HIGH TEMPERATURE RETURN

C

CIRCULATOR

2

0

4

0

° F

0

14

0

30

1

0

0

20

60

LEONARD

- 10

° C

0

10

50

1

2

0

40

R

60

80

HOT

WATER

SOURCE

COLD

SUPPLY

HEAT

TRAP

HIGH TEMPERATURE FIXTURES

SYSTEM FIXTURES

CIRCULATOR

AQUASTAT

BALANCING

VALVES

CHECK

FULL RETURN
LINE SIZE

VALVE #1

TEMPERED
RETURN

BALL VALVE FOR

SETUP (OPTIONAL)

C

T

ISOLATION

VALVE

CHECK

TEMPERED

VALVE #1

BALL

BALL
VALVE #2

Reviews: