Lenze · Decentralised frequency inverter 8400 motec (POWERLINK Option) · EDS84DMOTPL EN 1.0 - 11/2018
57
Parameter reference
Parameters relevant for POWERLINK communication
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13885
C13887
C13898
Parameter | Name:
C13885 | Suppress emergency message upon
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
The code controls the error response to failing PDO communication with a node. The failure is detected because ex-
pected PDO data are missing.
Selection list
(Lenze setting printed in bold)
0 Maintain PDO
1 Delete PDO
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13887 | Suppress emergency message upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
This code serves to suppress sending alarm messages to the managing node. You can explicitly suppress a certain
type of error. Furthermore, all errors are entered into the logbook.
• A change can only be effective immediately if no error number with the error type selected here is active in
C00165
.
Value is bit-coded:
Bit 0 Error
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13898 | 0x1F9A Host Name
Data type: VISIBLE_STRING
Index: 10677
d
= 29B5
h
The code defines a DNS-compatible device name. The length is limited to 20 characters.
The device name must be
non-ambiguous within the network domain.
Naming convention:
The device name ...
• starts with a letter;
• ends with a letter or a digit.
The device name consists of ...
• letters (A ... Z, a ... z);
• digits (0 ... 9);
• hyphen (-).
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT