15
Parameter reference
15.2
Parameter list
856
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00180
C00181
C00182
C00184
Parameter | Name:
C00180 | Running time
Data type: UNSIGNED_32
Index: 24395
d
= 5F4B
h
Display of various running times in seconds
Display range
(min. value | unit | max. value)
0
s
2147483647
Subcodes
Info
C00180/1
Runtime - control card
C00180/2
Running time - heatsink fan
C00180/3
Running time - internal fan
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00181 | Time settings
Data type: UNSIGNED_16
Index: 24394
d
= 5F4A
h
From version 06.00.00
Time for device search function (optical location)
Setting range
(min. value | unit | max. value)
0
s
6000
Subcodes
Lenze setting
Info
C00181/1
5 s
Time - device search function
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00182 | L_NSet_1: S-ramp time PT1
Data type: INTEGER_16
Index: 24393
d
= 5F49
h
FB
: PT1 S-ramp time for the main setpoint ramp function generator
• Only effective with activated ramp rounding (
= "1").
Setting range
(min. value | unit | max. value)
Lenze setting
0.01
s
50.00
20.00 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00184 | AutoFailReset repetition time
Data type: UNSIGNED_16
Index: 24391
d
= 5F47
h
After the time set here has expired, an error message of an error that has occurred will be reset automatically if
"AutoFailReset" had been configured correspondingly in
.
Setting range
(min. value | unit | max. value)
Lenze setting
1
s
600
3 s
Read access
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1