Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
777
11
System bus "CAN on board"
11.11
CANopen objects implemented | I-1A00
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1A00
The object I-1A00 serves to send parameter data as TPDO1.
[11-16] Data telegram assignment
IEC 61131 process data words are mapped. Only whole bytes can be mapped (1-byte/mapping
entry).
Related topics:
TPDO1 | "LP_CanOut1" port block
I-1A01
The object I-1A01 serves to send parameter data as TPDO2.
• For data telegram assignment, see object
Related topics:
TPDO2 | "LP_CanOut2" port block
Index:
I-1A00
Name:
TPDO1 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 4: Application object 1 ... 4
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 4
Mapping entries 1 ... 4 for TPDO1
• The 4th mapping entry is used for the statistic mapping. For this, there is no value
available.
8th byte
7th byte
6. byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 16
Bit 15 ... bit 8
Bit 7 ... bit 0
Index
Subindex
Length
Index:
I-1A01
Name:
TPDO2 mapping parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Number of mapped application
objects in PDO
0
0
8 rw
U8
1 ... 4: Application object 1 ... 4
0
0
4294967295 rw
U32
Subindex
Meaning
0
Number of mapped objects
1 ... 4
Mapping entries 1 ... 4 for TPDO2
• The 4th mapping entry is used for the statistic mapping. For this, there is no value
available.