17
Function library
17.1
Function blocks | L_PCTRL_1
1463
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Outputs
Parameters
Designator
Data type
Value/meaning
nOut_a
INT
Output signal
• Internal limitation to ±32767 (±199.99 %)
• Scaling: 16384
≡
100 %
bSetEqAct
INT
Status output "Setpoint and actual value are identical"
TRUE Setpoint and actual value are identical, i.e. no system deviation
available.
nPIDOut1_a
INT
PID controller output without influencing factor
nInfluence_a
• Inputs
bEnableInfluenceRamp
and
nInfluence_a
do not have any effect here, the
limited PID output value influenced by the internal ramp times is output.
• There is no connection with the additive input
nNSet_a
.
• Scaling: 16384
≡
100 %
nPIDOut2_a
INT
PID controller output with influencing factor
nInfluence_a
.
• There is no connection with the additive input
nNSet_a
.
• Scaling: 16384
≡
100 %
• Display parameter:
nInfluenceOut_a
INT
Current influencing factor ("ramp status") on the PID output value
• Scaling: 16384
≡
100 %
Parameters
Possible settings
Info
0.1
0.1
500.0 Gain Vp
• Lenze setting: 1.0
20
ms
6000 Reset time Tn
• Lenze setting: 400 ms
0.0
0.1
5.0 Differential component Kd
• Lenze setting: 0.0
-199.99
%
+199.99 MaxLimit
• Maximum value of the PID
operating range
• Lenze setting: 199.99 %
-199.99
%
+199.99 MinLimit
• Minimum value of the PID
operating range
• Lenze setting: -199.99 %
0.000
s
999.999 Acceleration time for the ramp at the
PID output (should be set as steep as
possible)
• Lenze setting: 0.010 s
0.000
s
999.999 Deceleration time for the ramp at the
PID output
• Lenze setting: 0.010 s
(Pos. Maximum)
(Pos. Minimum)
(Neg. Minimum)
(Neg. Maximum)
0.00
%
199.99 Operating range
• Determination of the operating
range for the PID process
controller by limiting the input
signal
nSet_a
.
• Lenze setting: No limitation (-
199.99 % ... +199.99 %)