Address
Name / setting range / [default setting]
Info
0x28C7:003
SLS Monitored: Output: SLS3 Monitored: Output
•
Read only
0 Deactivated
1 SD-Out1 positive logic
2 SD-Out1 negative logic
0x28C7:004
SLS Monitored: Output: SLS4 Monitored: Output
•
Read only
0 Deactivated
1 SD-Out1 positive logic
2 SD-Out1 negative logic
0x2907:001
Additional speed limitation
0 ... [0] ... 480000 rpm
0x500A:150
SLS1
0.0000 ... [0.0000] ... 214748.3647
0x500A:151
SLS1 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:152
SLS2
0.0000 ... [0.0000] ... 214748.3647
0x500A:153
SLS2 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:154
SLS3
0.0000 ... [0.0000] ... 214748.3647
0x500A:155
SLS3 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:156
SLS4
0.0000 ... [0.0000] ... 214748.3647
0x500A:157
SLS4 - deceleration time
0.000 ... [0.000] ... 2147483.647 s
0x500A:159
Compensation velocity of SLS
0.0000 ... [0.0000] ... 214748.3647
0x500A:160
Follower - Response to SLS
false Inactive
true Active
0x500A:161
Speed controller limitation (SLS)
false Inactive
true Active
0x500A:162
Deactivate safety functions
0x00000000 ... [0x00000000] ... 0xFFFFFFFF
Bit 1 Ignore SS1 request
Bit 2 Ignore SS2 request
Bit 3 Ignore SLS1-4 request
Bit 4 Ignore SDI request
0x500A:163
Limiter status
•
Read only
Bit 0 STO active
Bit 1 SS1 active
Bit 2 SS2 active
Bit 4 SLS1 active
Bit 5 SLS2 active
Bit 6 SLS3 active
Bit 7 SLS4 active
Bit 8 SDIpos active
Bit 9 SDIneg active
Safety functions
Safely-Limited Speed (SLS)
416