15.1
Basic setting
Preconditions
•
The wired communication with the inverter has been established.
•
If this condition is not met, read more detailed notes in section "
tion between inverter and »EASY Starter«
".
•
The PC with the installed »EASY Starter« is started.
Automatic configuration
By default, the engineering port of the inverter receives its IP address automatically from a
DHCP server. By pressing the "DHCP" button, the
parameter is active ("enabled").
Now, the IP configuration is completed. The inverter can be accessed via the Ethernet connec-
tion.
Manual configuration
Make sure to press the "Restart with current values" button every time you
change the values.
The engineering port must be configured when a static address is to be assigned.
For this purpose, the "DHCP" button must bet set to the "Disabled" state.
The following parameters can be entered in the »EASY Starter«:
•
IP address
•
Network mask
•
Gateway address
Using a configuration file
A file named "ip.txt" can be used to reset the IP address. This file must be stored on the SD
card in the root directory.
The network settings are evaluated and accepted when the inverter is started. The file is then
renamed as "ip_old.txt".
The structure of the text file can look as follows:
-
192.168.101.221
-
255.255.255.0
-
192.168.101.1
If the static IP address is to be reset to DHCP, only the content of the ip.txt file must be set to
"DHCP". This serves to use DCHP for a dynamic address allocation at next boot.
Parameter
Address
Name / setting range / [default setting]
Info
0x2450
Engineering port control
Activation of the engineering port settings (Ethernet).
0 No action/No error
1 Restart with current values
10 Busy
11 Cancelled
12 Faulted
0x2451:001
Engineering port settings: IP address
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Setting of the IP address.
The default setting 276605120 corresponds to the IP address
192.168.124.16.
•
276605120 = 0x107CA8C0
à
0xC0.0xA8.0x7C.0x10 = 192.168.124.16
0x2451:002
Engineering port settings: Subnet
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Setting of the subnet mask.
The default setting 16777215 corresponds to the subnet mask
255.255.255.0.
•
16777215 = 0xFFFFFF
à
0xFF.0xFF.0xFF.0x00 = 255.255.255.0
Configure engineering port
Basic setting
313