Brake polarity
The control logic of the holding brake can be inverted.
Parameter
Address
Name / setting range / [default setting]
Info
0x2820:001
Holding brake control: Brake mode
Selecting how the "Release holding brake" command is to be triggered.
0 Automatically (via device state)
Automatic operation: depending on the device state, the "Release hold-
ing brake" command is given automatically if the controller is to be ena-
bled.
1 Manually
Depending on the TA, the "Release holding brake" command can also be
initiated by the following external triggers:
TA Cia:
TA Speed Control: bit 10
2 Off
The holding brake is deactivated.
0x2820:002
Holding brake control: Brake closing time
0 ... [100] ... 10000 ms
Application time (engagement time) of the holding brake.
•
Only effective in automatic operation.
0x2820:003
Holding brake control: Brake opening time
0 ... [100] ... 10000 ms
Release time (disengagement time) of the holding brake.
•
Only effective in automatic operation.
0x2820:004
Holding brake control: Brake detection
•
Read only
When
= 4 (Manual control mode) and the device state changes
from "switched-on" to "operation enabled", it is detected automatically
whether a holding brake is connected. The brake identification is repea-
ted after every controller enable.
0 Detection not started
1 Detection running
2 No brake detected
3 Brake detected
0x2820:005
Holding brake control: Brake polarity
The control logic of the holding brake can be inverted.
0 Normal
1 Inverted
0x2820:006
Holding brake control: Brake error response
Selection of the response for holding brake monitoring.
In the triggered state, the holding brake is monitored cyclically for the
presence of brake current.
After the brake is connected, the establishment of the brake current is
subject to a time delay in accordance with the inductance. Consequently,
there is a slight delay in detecting wire breakage, a terminal short-circuit
or a missing brake supply.
The response set here occurs when monitoring is triggered.
Note:
The brake is not monitored unless it is triggered.
0 No fault
1 Fault
2 Warning
0x2820:015
Holding brake control: Brake status
•
Read only
Display of the holding brake status.
•
The status is also displayed via bit 14 in the CiA: Statusword
0 Active
Holding brake is applied.
1 Brake released
Holding brake is released.
0x2820:019
Holding brake control: Brake opening time test signal
0 ... [500] ... 10000 ms
Setting of the brake opening time when the test signal is transmitted
(Brake control word bit 0 = 1).
0x2820:022
Holding brake control: Versorgungsspannung Halte-
bremse
75 Absenkung auf 75%
100 Keine Absenkung
Further setting options:
•
13.5.3.2
Brake holding load
Parameter
Address
Name / setting range / [default setting]
Info
0x2820:013
Holding brake control: Holding load ramptime
0 ... [0] ... 1000 ms
By setting a ramp time, a vibration stimulation can be reduced that
might be caused by the brake holding load .
Configuring the motor control
Parameterisable motor functions
Holding brake control
255