Technical data
Rated data
l
32
EDKZS3YA200 DE/EN/FR/ES/IT 3.0
Mounting conditions
Mounting place
In the control cabinet, as close as possible to the
controller
Mounting position
Dependent on the payload of the control cabinet wall
Lightweight filters: suspended, fixing bracket to the
sides
Heavy filters: vertical, fixing bracket below
Free space
100 mm to the side and above
Connecting cables
Controller
«
filter
As short as possible, shielded
Filter
«
motor
Max. 200 m shielded or max. 300 m unshielded
4.2
Rated data
Voltage
Output
frequency
Switching
frequency
Rate of rise of
voltage
U [V AC]
f [Hz]
f
ch
[kHz]
du/dt [V/
m
s]
EZS3−xxxA200
0 ... 550
0 ... 150
2 ... 4
< 500
Current
Power loss
Inductance
I
N
[A]
P
V
[W]
L [mH]
EZS3−115A200
115
360
0.7
EZS3−150A200
150
400
0.5