Technical data
2.1
General data and operating conditions
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
IT systems
Max. mains voltage 400 V!
Observe instructions for special measures in the
documentation for the basic device!
Protection
Degree of protection
EN 60529
IP 20
Not in the wire range of
the terminals
Insulation resistance
EN 61800−5−1
Overvoltage category III
> 2000 m: Overvoltage category II
Leakage current
EN 61800−5−1
> 3.5 mA
Observe regulations and
safety instructions!
Ambient conditions
Temperature
Storage
−25 ... +60 °C
Transport
−25 ... +70 °C
Operation
−10 ... +55 °C
Current derating from +40 to +55 °C: 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating by 5 %/1000 m
Pollution
EN 61800−5−1
Pollution degree 2
Vibration resistance
EN 50178; IEC
61800−5−1;
Germanischer Lloyd,
general conditions
Acceleration−resistant up to 0.7 g
Mounting conditions
Mounting location
In the control cabinet
Mounting position
Directly above the basic device
Mounting position
Vertical, mains connection on top
Free spaces
at the top
> 50 mm
to the sides
> 50 mm