Error messages
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
EtherNet/IP: Invalid Configuration [0x01bc6430]
EtherNet/IP: Invalid IP Parameters [0x01bc6533]
EtherNet/IP: Fault Mode [0x01bc8111]
EtherNet/IP: Explicit Message Timeout [0x01bc8112]
EtherNet/IP: Overall Ethernet Timeout [0x01bc8114]
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
Module configuration is faulty.
Check and correct module configuration.
Response
(Lenze setting printed in bold)
Setting:
not possible
No reaction
System fault
Fault
Trouble
Quick stop by trouble
WarningLocked
Warning
Information
Cause
Remedy
One or more IP parameters are faulty.
Check and correct IP configuration.
Setting the IP configuration of the Inverter Drive 8400
Response
(Lenze setting printed in bold)
Setting:
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
• Connection to scanner has been interrupted.
• Controlling I/O connection failed by timeout.
• Within the timeout time for implicit messages
parameterised by the scanner, no "implicit messages"
have been received.
• Check cables and terminals.
• Plug the network cable into the EtherNet/IP terminal.
• Check Requested Package Interval (RPI) of I/O
connection.
• Increase timeout time for implicit messages.
Response
(Lenze setting printed in bold)
Setting:
No reaction
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Connection to scanner has been interrupted.
• Failure of an explicit connection
• Within the timeout time for explicit messages
parameterised by the scanner, no "explicit messages"
have been received.
• Check cables and terminals.
• Plug the network cable into the EtherNet/IP terminal.
• Check Requested Package Interval (RPI) of the explicit
connection.
• Increase timeout time for explicit messages.
Response
(Lenze setting printed in bold)
Setting:
No reaction
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• Failure of »Engineer« communication via Ethernet
• When the time set in
has expired, there is no
access via the »Engineer«.
• Check cables and terminals.
• Plug in network cable.
• Increase the overall Ethernet timeout time in
.