Technical data
General data and operating conditions
EDK10203EZ3 DE/EN/FR 4.1
13
H1_Daten−All_Data_Ext−board_en
3
Technical data
General data and operating conditions
Conformity
CE
Low−Voltage Directive (2006/95/EC)
Approvals
UL 508C
Underwriter Laboratories (File−No. E132659)
Power Conversion Equipment
DC supply voltage
Voltage
ex18 VDC −0 % ... +30 VDC +0 %
Current
max. 4 A
(at max. load of all outputs)
Climatic conditions
Class 3K3 to EN 50178
(without condensation, average relative humidity 85 %)
Temperature range
Transport
−25 °C ... +70 °C
storage
−25 °C ... +60 °C
Operation
0 °C ... +40 °C without power derating
+40 °C ... +55 °C with power derating
Power derating
of output currents for t
a
> +40 °C: 2.5 %/K
Vibration resistance
Resistant to acceleration up to 0.7 g
Permissible mounting
positions
in the Drive PLC on a plug−in−station for extension board
Insulation voltage to PE
50 V AC
Enclosure
IP 20
Digital inputs
Level
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current
8 mA at 24 V
Digital outputs
Level
LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity
max. 1 A per output
Analog inputs
Input voltage
−10 V ... +10 V
Resolution
10 bit + sign
Incremental encoder/
meter input
Connection
SubD bush, 9−pole
HTL level
Input frequency: 0 − 200 kHz
Current input per channel: 5 mA
TTL level
Input frequency: 0 − 500 kHz
Current input per channel: 6 mA
Current input at pin 4 (V
CC5_E
): max. 150 mA
Dimensions
Height
145 mm (incl. terminal strips)
Width
72 mm
Depth
35 mm