Commissioning
Setting of mains data
Setting the voltage thresholds
99
EDBCSXS064 EN 4.0
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0175 UG−Relais Fkt
1
Charge relay behaviour with
undervoltage (LU) in the DC bus.
1
Standard
Relay switches as a function of
LU.
2
One Time
Relay switches when LU is
exceeded for the first time and
remains on.
3
Fixed On
Charging current limitation is
inactive.
l
Relay is always switched on
and the charging resistors of
the axis module are thus
permanently jumpered.
l
Setting for operation with
ECSxE power supply module.
6.5.2
Setting the voltage thresholds
Note!
All drive components in DC−bus connections must have the same thresholds!
Selection
Mains voltage
Brake unit
LU message
(Undervoltage)
OU message
(Overvoltage)
C0173
Power supply module
[V AC]
Setting
[V DC]
Resetting
[V DC]
Setting
[V DC]
Resetting
[V DC]
0
230
yes/no
130
275
400
390
1
400
yes/no
285
430
800
790
2
400 ... 460
yes/no
328
473
800
790
3
480
no
342
487
800
785
4
480
yes
342
487
800
785
10
230
yes/no
C0174
C0174 + 5 V
400
390
11
400 (Lenze setting)
yes/no
C0174
C0174 + 5 V
800
790
12
400 ... 460
yes/no
C0174
C0174 + 5 V
800
790
13
480
no
C0174
C0174 + 5 V
800
785
14
480
yes
C0174
C0174 + 5 V
800
785
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0174 UG min
60
Undervoltage threshold of DC
bus (LU)
15
{1 V}
342