Electrical installation
Control terminals
Digital inputs and outputs
69
EDBCSXS064 EN 4.0
5.3.1
Digital inputs and outputs
Stop!
If an inductive load is connected to X6/DO1, a spark suppressor with a limiting
function to max. 50 V
±
0 % must be provided.
DI1 DI2 DI3 DI4
47k
GNDext
3k3
3k3
3k3
3k3
GND
DO1
X6
1.5
A
1k
+
_
24 VDC =
+24
"
"
ECSXA014
Fig. 5−9
Digital inputs and outputs at X6
HF−shield termination by large−surface connection to functional earth (see Mounting
Instructions for ECSZS000X0B shield mounting kit)
ƒ
The digital inputs X6/DI1 ... DI4 are freely assignable.
ƒ
The polarity of the digital inputs X6/DI1 ... DI4 is set under C0114/x.
ƒ
The polarity of the digital output (X6/DO1) is set under C0118/1.