Function library
AIn1
266
EDBCSXS064 EN 4.0
12.8
AIn1
Function
This function block provides the interface for analog input signals (differential signals) via
X6/AI−, AI+. The conditioned input signal is available at the function block output. When
using X6/AI−, AI+ as a master current input, cable−break monitoring is possible.
AI-
AI+
AG
X6
AIn1
C0034
C0026/1
C0027/1
920
920
C0400
AIn1-Out
AIn1-Error
ECSXA221
Fig. 12−8
AIn1 function block
Codes
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0026
Offset for relative analog signals
(AIN)
266
1 FCODE(offset)
0,0
−199,99
{0.01 %}
199,99 FCODE_nC26_1_a
2 FCODE(offset)
0,0
FCODE_nC26_2_a
C0027
Gain for relative analog signals
(AIN)
266
1 FCODE(gain)
100,0
−199,99
{0.01 %}
199,99 FCODE_nC27_1_a
2 FCODE(gain)
100,0
FCODE_nC27_2_a
C0034 Mst current
0
Master voltage/master current
on analog input (AIN1_nIn_a)
266
0
−10 ... + 10 V
Master voltage
1
+4 ... +20 mA
Master current
2
−20 ... +20 mA
C0400 DIS: AnalogIn
Signal at the analog input
Read only
266
−199.99
{0.01 %}
199.99