Diagnostics
LED status displays
8
EDK94AYCIB DE/EN/FR/ES/IT 2.0
55
H1_Diagnose−Statusanzeige
8
Diagnostics
LED status displays
E94YCIB001F
LED
Description
Pos.
Colour
Condition
MS
green
flashes
The communication module is being supplied with voltage but is
not connected to the standard device. (The standard device has
been switched off in the initialisation phase or does not exist.)
MS
green
on
The communication module is being supplied with voltage and is
connected to the standard device.
ME
red
on
There is a fault in the area of the communication module.
BS
green
off
The communication module is not active on the field bus. Data
cycles are not being executed.
flashes
Communication via the communication module has been set up.
The INTERBUS is active. Data cycles are being executed.
BE
red
flashes
Impermissible setting:
l
Total number of data words (PD + PCP) > 10
l
Total number of data words (PD + PCP) = 0
The communication module has been initialised and is working
internally with the following values:
l
PD = 2 (words)
l
PCP = 1 (word)
on
INTERBUS communication interrupted. Data cycles are not being
executed.
DE
red
on
The communication module is not accepted by the standard
device (see notes in the documentation for the standard device)
or the standard device is not active.
Summary of Contents for E94AYCIB
Page 2: ... DUMMYSEITEVOR ...
Page 4: ...EDK94AYCIB DE EN FR ES IT 2 0 4 klappseite E94AYCIB E94YCIB001B ...
Page 30: ...EDK94AYCIB DE EN FR ES IT 2 0 30 klappseite E94AYCIB E94YCIB001B ...
Page 56: ...EDK94AYCIB DE EN FR ES IT 2 0 56 klappseite E94AYCIB E94YCIB001B ...
Page 82: ...EDK94AYCIB DE EN FR ES IT 2 0 82 klappseite E94AYCIB E94YCIB001B ...
Page 108: ...EDK94AYCIB DE EN FR ES IT 2 0 108 klappseite E94AYCIB E94YCIB001B ...