Electrical installation
Wiring
EDK82ZAFSC DE/EN/FR 5.0
39
H2_verdrahtung−INS_Klemmenbeleg
X3/
Signal
type
Function
(Lenze setting: bold print)
Level
(Lenze setting: bold print)
62
Analog
output
Output frequency
0 +6 V
0 +10 V
1)
7
−
GND1,
Reference potential for analog signals
−
8
Analog
input
Input for actual value or setpoint
Switch over the range with the DIP switch and in C0034:
l
Voltage signal
0 +5 V
0 +10 V
−10 +10 V
2)
l
Current signal
0 +20 mA
+4 +20 mA
+4 +20 mA (open−circuit
monitored)
9
−
Internal, stabilised DC voltage source for the
setpoint potentiometer
+5.2 V
20
−
Internal DC voltage supply for control of digital
inputs and outputs
+20 V ±10 % (ref.: X3/7)
28
Digital
inputs
Controller inhibit (CINH)
1 = enable
E1
3)
Activation of JOG frequencies
JOG1 = 20 Hz
JOG2 = 30 Hz
JOG3 = 40 Hz
e1
E2
JOG1
1
0
E2
3)
JOG2
0
1
JOG3
1
1
E3
DC−injection brake (DCB)
1 = DCB
E4
Change of direction of rotation
CW/CCW rotation
E4
CW
0
CCW
1
39
−
GND2,
Reference potential for digital signals
−
A1
Digital
output
Ready for operation
l
internal supply:
l
external supply:
0 +20 V
0 +24 V
59
−
DC supply for X3/A1
l
internal (bridge to X3/20):
l
external:
+20 V
+24 V
1)
Output level 0 +10 V: Adapt offset (C0109/C0422) and gain (C0108/C0420)
2)
Adjust offset (C0026) and gain (C0027) separately for each function module ...
− after replacing the function module or the basic device.
− after loading the Lenze setting.
3)
Frequency input alternatively 0 10 kHz single−track or 0 ... 1 kHz two−track, config. via C0425
Summary of Contents for E82ZAFSC
Page 3: ...ausklappbild E82ZAFS002A ...