Codetabelle
Communication−relevant Lenze codes
l
59
EDS82ZAFIC EN 2.0
C1511:
Configuring process output data
Code
C1511
Name
Configuring process output data
Index
0x5A18 (23064)
Subcode
Lenze
Values
Access
Data type
1
POW1
17
see table below
rw
FIX32
2
POW2
3
3
POW3
4
4
POW 4
5
þ
Parameter set transfer
The assignment of the max. 4 process output data words (POW) of the master to bit control
commands or setpoints of the controller can be configured freely using C1511.
)
Note!
For reasons of compatibility, subcodes 5 and 6 can also be read and written
with modules from software version V3.0. However, this has no effect.
Selection
Scaling
1
FIF control word 1 (FIF−CTRL1)
16 bits
2
FIF control word 2 (FIF−CTRL2)
16 bits
3
Setpoint 1 (NSET1−N1)
±24000
º
±480 Hz
4
Setpoint 2 (NSET1−N2)
±24000
º
±480 Hz
5
Additional setpoint (PCTRL1−NADD)
±24000
º
±480 Hz
6
Actual process controller value (PCTRL1−ACT)
±24000
º
±480 Hz
7
Process controller setpoint (PCTRL1−SET1)
±24000
º
±480 Hz
8
reserved
9
Torque setpoint / limit value (MCTRL1−MSET)
2
14
º
100 % rated motor torque
10
PWM voltage (MCTRL1−VOLT−ADD)
(
Only for special applications. Modifications only
after consulting Lenze!
11
PWM angle (MCTRL1−PHI−ADD)
12
reserved
13
FIF−IN.W1
16 bits or 0 ... 65535
14
FIF−IN.W2
16 bits or 0 ... 65535
15
FIF−IN.W3
0 ... 65535
16
FIF−IN.W4
0 ... 65535
17
DRIVECOM control word (DRIVECOM−CTRL)
16 bits