Process data transfer
Lenze device control
Process data signals for 8200 vector / 8200 motec
l
39
EDS82ZAFIC EN 2.0
Configuring process input data
The assignment of the bit status information or actual values of the controller to the max.
4 process input data words (PIW) of the master can be configured freely:
ƒ
In order to access DRIVECOM−compliant status information, assign the DRIVECOM
status word to a PIW (C1511/x = 18).
ƒ
The FIF status word1 is mapped to the DRIVECOM status word.
Configuration of the process input data
Code
C1510
Name
Configuring process input data
Index
0x5A19 (23065)
Subcode
Lenze
Access
Data type
1
PIW1
18
DRIVECOM status word (DRIVECOM−STAT)
rw
FIX32
2
PIW2
3
Output frequency with slip (MCTRL1−NOUT+SLIP)
rw
FIX32
3
PIW3
4
Output frequency without slip (MCTRL1−NOUT)
rw
FIX32
4
PIW4
5
Apparent motor current (MCTRL1−IMOT)
rw
FIX32
þ
Parameter set transfer
I
Tip!
For a detailed description of the code, see
^