Montageanleitung

Mounting Instructions

Instructions de montage

EDK82ZAFBC−201

.B,8

Ä.B,8ä

8200 motec 

3.0 ... 7.5 kW

l

E82ZAFBC201

Bus−I/O

Bus−I/O

Bus E/S

    

    

Global Drive

  

     

Summary of Contents for E82ZAFBC201

Page 1: ...Montageanleitung Mounting Instructions Instructions de montage EDK82ZAFBC 201 B 8 B 8 8200 motec 3 0 7 5 kW l E82ZAFBC201 Bus I O Bus I O Bus E S Global Drive...

Page 2: ...die enthaltenen Sicherheitshinweise Please read these instructions and the documentation of the standard device before you start working Observe the safety instructions given therein Lire le pr sent f...

Page 3: ...59 E82ZAFBC201 0 1 2 E82ZAFB015 Funktionsmodul E82ZAFBC201 0 Schalter zur Konfigurierung des Analogeingangs Klemme X3 8 20 1 Digitale und analoge Ein und Ausg nge Steckerleiste X3 18 2 Typenschild 4...

Page 4: ...2ZAFBC2013B Diese Anleitung ist nur g ltig zusammen mit der zugeh rigen Dokumentation der f r den Einsatz zul ssigen Grundger te Identifikation E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 APPLICATIO...

Page 5: ...it Das Funktionsmodul E82ZAFBC201 ist einsetzbar mit folgendem Grundger t und folgenden Feldbus Funktionsmodulen Typ Bezeichnung ab Version Frequenzumrichter 8200 motec 3 0 7 5 kW VB21 Feldbus Funktio...

Page 6: ...aten 9 Allgemeine Daten und Einsatzbedingungen 9 Anschlussdaten 10 Abmessungen 11 3 Lieferumfang 12 4 Mechanische Installation 13 5 Elektrische Installation 14 EMV gerechte Verdrahtung 14 Verdrahtung...

Page 7: ...iktogramm und Signalwort Bedeutung Gefahr Gefahr von Personensch den durch gef hrliche elektri sche Spannung Hinweis auf eine unmittelbar drohende Gefahr die den Tod oder schwere Verletzungen zur Folg...

Page 8: ...se Piktogramm und Signalwort Bedeutung Hinweis Wichtiger Hinweis f r die st rungsfreie Funktion I Tipp N tzlicher Tipp f r die einfache Handhabung Verweis auf andere Dokumentation Restgefahren Gefahr...

Page 9: ...probation UL UL 508C Industrial Control Equipment File No E132659 CSA CSA 22 2 No 14 Personenschutz und Ger teschutz Schutzart EN 60529 IP20 Einsatzbedingungen Umgebungsbedingungen Klimatisch Lagerung...

Page 10: ...stand l REingang 50 kW bei Spannungssignal l REingang 250 W bei Stromsignal 9 Belastbarkeit Imax 10 mA 7 potenzialgetrennt zu Klemme X3 39 GND2 20 Belastbarkeit S Imax 40 mA 28 Eingangswiderstand 3 3...

Page 11: ...Technische Daten Abmessungen 2 EDK82ZAFBC 201 DE EN FR 5 1 11 l H1_Daten AlleMa eInMM Abmessungen 1 1 2 2 3 3 4 4 5 5 62 7 7 8 9 20 28 E1 E2 E3 E4 39 A1 59 64 57 15 E82ZAFB009 alle Ma e in mm...

Page 12: ...EDK82ZAFBC 201 DE EN FR 5 1 12 l H1_LIF E82ZAFBC201_Liefer_BL 3 Lieferumfang 1 2 S Standard I O 0 E82ZAFB210 Pos Lieferumfang siehe 0 Bus I O Funktionsmodul E82ZAFBC201 1 Schraubendreher 2 Aufkleber M...

Page 13: ...op Das Bus I O Funktionsmodul muss auf Steckplatz 1 gesteckt werden 0 1 E82ZAFB202 1 Schutzkappen der Funktionsmodule entfernen 2 Bus I O Funktionsmodul 0 in motec Tr gergeh use auf Steckplatz 1 einse...

Page 14: ...men f hren ungeschirmte Aderl nge 40 mm Legen Sie die Schirme der Steuerleitungen bzw Datenleitungen wie folgt auf Einseitig am Umrichter bei Leitungen mit analogen Signalen Beidseitig bei Leitungen m...

Page 15: ...ca 10 cm entfernen Schirm mit Kabelbinder auf Schirmblech auflegen Feldbus Funktionsmodul verdrahten siehe dazugeh rige Montageanleitung Klemme 28 Reglersperre des Bus Funktionsmoduls 0ist inaktiv Re...

Page 16: ...n Bereich Werte Elektrischer Anschluss Klemmenleiste mit Schraubanschluss Anschlussm glichkeiten starr 1 5 mm2 AWG 16 flexibel ohne Aderendh lse 1 0 mm2 AWG 18 mit Aderendh lse ohne Kunststoffh lse 0...

Page 17: ...5V 20V 8 9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 7 E82ZxFB004 Versorgung ber eine externe Spannungsquelle X3 28 Reglersperre CINH X3 E1 X3 E4 digitale Eing nge Bus I O Funktionsmodul Feldbus Funktionsm...

Page 18: ...usg nge 20 V 10 Bezug X3 7 28 Digitale Eing nge Reglersperre CINH 1 Freigabe E1 3 Aktivierung von Festfrequenzen JOG JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz E1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3 Gleichstr...

Page 19: ...n motec und die Funktionsmodule nicht zu besch digen unbedingt vor dem Zusammenbau die Schutzkappe jedes Funktionsmoduls 1 entfernen und aufbewahren die FIF Abdeckkappe 0 entfernen und aufbewahren Vor...

Page 20: ...Hinweis Die DIP Schalter und C0034 unbedingt auf den gleichen Bereich einstellen da sonst das analoge Eingangssignal an X3 8 durch das Grundger t falsch interpretiert wird Wird ein Sollwertpotentiomet...

Page 21: ...H Pegel an X3 28 anliegt Reglerfreigabe ber Klemme Beachten Sie dass die Reglersperre ber mehrere Quellen gesetzt werden kann Die Quellen wirken wie eine Reihenschaltung von Schaltern Wenn der Antrieb...

Page 22: ...7 Inbetriebnahme Mit Lenze Einstellung EDK82ZAFBC 201 DE EN FR 5 1 22 l H1inbet DUMMYSEITEVOR...

Page 23: ...59 E82ZAFBC201 0 1 2 E82ZAFB015 E82ZAFBC201 function module 0 Switch for the configuration of the analog input terminal X3 8 40 1 Digital and analog inputs and outputs plug connector X3 38 2 Nameplat...

Page 24: ...on E82ZAFBC2013B These instructions are only valid together with the documentation for the standard devices permitted for the application Identification E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 A...

Page 25: ...ge The E82ZAFBC201 function module can be used together with the following basic device and the following fieldbus function modules Type Designation as of version Frequency inverter 8200 motec 3 0 7 5...

Page 26: ...cal data 29 General data and operating conditions 29 Connection data 30 Dimensions 31 3 Scope of supply 32 4 Mechanical installation 33 5 Electrical installation 34 EMC compliant wiring 34 Wiring 35 6...

Page 27: ...o prevent dangerous situations Pictograph and signal word Meaning Danger Danger of personal injury through dangerous electrical voltage Reference to an imminent danger that may result in death or seri...

Page 28: ...on notes Pictograph and signal word Meaning Note Important note to ensure troublefree operation I Tip Useful tip for simple handling Reference to another documentation Residual hazards Danger Observe...

Page 29: ...C Industrial Control Equipment File No E132659 CSA CSA 22 2 No 14 Protection of persons and equipment Type of protection EN 60529 IP20 Operating conditions Ambient conditions Climate Storage IEC EN 60...

Page 30: ...60 C Input resistance l RInput 50 kW with voltage signal l RInput 250 W with current signal 9 Carrying capacity Imax 10 mA 7 isolated from terminal X3 39 GND2 20 Load capacity S Imax 40 mA 28 Input re...

Page 31: ...Technical data Dimensions 2 EDK82ZAFBC 201 DE EN FR 5 1 31 l H1_Daten AlleMa eInMM Dimensions 1 1 2 2 3 3 4 4 5 5 62 7 7 8 9 20 28 E1 E2 E3 E4 39 A1 59 64 57 15 E82ZAFB009 All dimensions in mm...

Page 32: ...DK82ZAFBC 201 DE EN FR 5 1 32 l H1_LIF E82ZAFBC201_Liefer_BL 3 Scope of supply 1 2 S Standard I O 0 E82ZAFB210 Pos Scope of supply see 0 E82ZAFBC201 bus I O function module 1 Screw driver 2 Sticker Mo...

Page 33: ...I O function module has to be plugged into receptacle 1 0 1 E82ZAFB202 1 Remove protecting caps of function modules 2 Insert bus I O function module 0 into receptacle 1 of motec carrier housing until...

Page 34: ...ded core length 40 mm Connect control and data cable shields as follows Analog signal cable shields must be connected with one end at the inverter Digital signal cable shields must be connected with b...

Page 35: ...the shield to the shield sheet using the cable tie Wire the fieldbus function module see corresponding Mounting Instructions Terminal 28 controller inhibit of the bus function module 0 is inactive Co...

Page 36: ...ctrical connection Terminal strip with screw connection Possible connections rigid 1 5 mm2 AWG 16 flexible without wire end ferrule 1 0 mm2 AWG 18 with wire end ferrule without plastic sleeve 0 5 mm2...

Page 37: ...V 20V 8 9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 7 E82ZxFB004 Supply via an external voltage source X3 28 controller inhibit CINH X3 E1 X3 E4 digital inputs Bus I O function module Fieldbus function modu...

Page 38: ...s and outputs 20 V 10 ref X3 7 28 Digital inputs Controller inhibit CINH 1 enable E1 3 Activation of JOG frequencies JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz e1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3 DC inject...

Page 39: ...rder to avoid damages of the motec and the function modules proceed as follows before starting to assemble Remove and keep the protecting cap of each function module 1 Remove and keep the FIF cap 0 Co...

Page 40: ...to set the DIP switch and C0034 to the same range otherwise the analog input signal at X3 8 will be interpreted incorrectly by the basic device If a setpoint potentiometer is supplied internally via X...

Page 41: ...ing if a HIGH level is applied to X3 28 controller release via terminal Please observe that the controller can be inhibited through various sources All sources act like a series connection of switches...

Page 42: ...7 Commissioning Commissioning using Lenze settings EDK82ZAFBC 201 DE EN FR 5 1 42 l H1inbet DUMMYSEITEVOR...

Page 43: ...FB015 Module de fonction E82ZAFBC201 0 Interrupteur pour la configuration de l entr e analogique borne X3 8 60 1 Entr es et sorties num riques et analogiques bornier enfichable X3 58 2 Plaque signal t...

Page 44: ...version E82ZAFBC2013B Ce document est uniquement valable avec la documentation relative aux appareils de base compatibles Identification E82AF000P0B201XX APPLICATION 010 3A22 A22 A22 APPLICATION 010 3...

Page 45: ...e utilis sur les appareils de base et conjointement avec les modules de fonction bus de terrain suivants Type D signation A partir de la version Convertisseurs de fr quence 8200 motec 3 0 7 5 kW VB21...

Page 46: ...ract ristiques g n rales et conditions d utilisation 49 Donn es de raccordement 50 Encombrements 51 3 Equipement livr 52 4 Installation m canique 53 5 Installation lectrique 54 C blage conforme CEM 54...

Page 47: ...Situation dangereuse pour les personnes en raison d une tension lectrique lev e Indication d un danger imminent qui peut avoir pour cons quences des blessures mortelles ou tr s graves en cas de non re...

Page 48: ...associ Explication Remarque importante Remarque importante pour assurer un fonctionnement correct I Conseil Conseil utile pour faciliter la mise en uvre Renvoi une autre documentation Dangers r sidue...

Page 49: ...UL 508C Industrial Control Equipment File No E132659 CSA CSA 22 2 No 14 Protection des personnes et protection de l appareil Indice de protection EN 60529 IP20 Conditions d utilisation Conditions amb...

Page 50: ...l REntr e 50 kW signal de tension l REntr e 250 W signal de courant 9 Capacit de charge Imax 10 mA 7 Avec s paration de potentiel sur la borne X3 39 GND2 20 Charge admissible S Imax 40 mA 28 R sistanc...

Page 51: ...ications techniques Encombrements 2 EDK82ZAFBC 201 DE EN FR 5 1 51 l H1_Daten AlleMa eInMM Encombrements 1 1 2 2 3 3 4 4 5 5 62 7 7 8 9 20 28 E1 E2 E3 E4 39 A1 59 64 57 15 E82ZAFB009 Toutes les cotes...

Page 52: ...BC 201 DE EN FR 5 1 52 l H1_LIF E82ZAFBC201_Liefer_BL 3 Equipement livr 1 2 S Standard I O 0 E82ZAFB210 Pos Contenu de l emballage voir 0 Module de fonction bus E S E82ZAFBC201 1 Tournevis 2 Autocolla...

Page 53: ...r imp rativement le module de fonction bus E S sur le point d acc s 1 0 1 E82ZAFB202 1 Enlever les capots de protection des modules de fonction 2 Encliqueter le module de fonction bus E S 0 dans l emb...

Page 54: ...s blindage 40 mm Pour poser les blindages des c bles de commande ou des lignes de donn es proc dez comme suit D un seul c t du convertisseur pour les c bles avec des signaux analogiques Des deux c t s...

Page 55: ...avec serre c ble sur la t le de blindage C bler le module de fonction bus de terrain voir instructions de montage aff rentes La borne 28 blocage variateur du module de fonction bus 0 n est pas activ...

Page 56: ...ment Plage Valeurs Raccordement lectrique Bornier avec fixation par vis Possibilit s de raccordement Rigide 1 5 mm2 AWG 16 Flexible sans embout 1 0 mm2 AWG 18 avec embout sans cosse en plastique 0 5 m...

Page 57: ...9 7 0 5 V 1k 10k AIN1 AOUT1 DIGOUT1 7 7 E82ZxFB004 Alimentation via une source de tension externe X3 28 blocage variateur CINH X3 E1 X3 E4 entr es num riques Module de fonction bus E S Module de fonct...

Page 58: ...iques 20 V 10 r f rence X3 7 28 Entr es num riques Blocage variateur CINH 1 D blocage E1 3 Activation des fr quences fixes JOG JOG1 20 Hz JOG2 30 Hz JOG3 40 Hz E1 E2 JOG1 1 0 E2 3 JOG2 0 1 JOG3 1 1 E3...

Page 59: ...es afin de prot ger le motec et le module de fonction bus E S contre tout endommagement enlever le capot de protection du module de fonction bus E S 1 et le conserver pr cieusement retirer le capot de...

Page 60: ...rqueimportante R gler imp rativement l interrupteur DIP et C0034 sur la m me plage dans le cas contraire le signal d entr e analogique sur X3 8 sera mal interpr t par l appareil de base Si un potentio...

Page 61: ...actif sur la borne X3 28 d blocage variateur via borne Veillez ce que le blocage variateur puisse tre d fini par le biais de plusieurs sources Ces sources agissent comme des contacts connect s en s ri...

Page 62: ...tra e 3 D 32699 Extertal Germany Service Lenze Service GmbH Breslauer Stra e 3 D 32699 Extertal Germany 49 5154 82 0 008000 2446877 24 h helpline 49 5154 82 2800 49 5154 82 1112 lenze lenze com servic...