EtherCAT: Sync telegram failure [0x00c88700]
Response
(Lenze setting printed in bold)
/
(
Configurable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
Warning
Information
Cause
Remedy
• EtherCAT-Sync0 signal has failed.
• PDO sent or received too late as the instant of
transmission of the EtherCAT frame by the master
jitters too much.
• Check EtherCAT master configuration if the DC mode
has been set.
• Restart EtherCAT configuration.
• Postpone PDO instant of reception via the user shift
time.
• Increase sync error counter monitoring limit
(0x10F1.2).