Configuration
Basic configuration
2−4
l
EDSVF9383V−EXT EN 2.0
2.2
Basic configuration
(
Stop!
Under code C0005 you can load predefined basic configurations. If the
configuration is changed via C0005, all input and output assignments will be
overwritten with the corresponding basic configuration. If necessary, adapt the
function assignment to your wiring.
For adapting the function assignment to a certain wiring or extended signal
processing, please see the chapter "Use of function blocks".
A predefined basic configuration is selected to adapt the internal signal processing to your drive task
(e.g. step control or dancer position control). Using the default setting, you can e.g. already control
the speed of the drive.
l
For a detailed description of the individual basic configurations, terminal assignments, signal
flow charts and applications examples, please see the chapter "Application examples".
l
Before loading the basic configuration under C0005, the controller must be inhibited.
Under C0005, you can select and activate predefined basic configurations. A four−digit number is
used for selection with specific characteristics being assigned to each digit.
First digit
Defines the basic function of the configuration.
Configuration of C0005
Basic function
1xxx
Speed control
2xxx
Step control
3xxx
Traversing control
4xxx
Torque control
5xxx
Digital frequency master
6xxx
Digital frequency slave (bus)
7xxx
Digital frequency slave (cascade)
8xxx
Dancer position control (external diameter detection)
9xxx
Dancer position control (internal diameter detection)