RG-MHMOD 22
Drive Control & Communication
AC Tech
Register
Number
(hexadecimal
representation)
Parameter
1
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory Default
77 (4D)
26
STOP
00 - Ramp
01 - Coast
00 - Coast
79 (4F)
28
SPEED SRC KEY
00 - Enabled
01 - Disabled
00 - Enabled
80 (50)
29
HAND SRC
00 - Keypad
01 - 0-10 VDC
02 - 4-20mA
03 - Preset #1
04 - Preset #2
05 - Preset #3
06 - Preset #4
07 - MOP
08 - Selected
00 - Keypad
81 (51)
30
CONTROL
00 - Normal
01 - Normal / No Hand
02 - Serial Speed
03 - Serial Speed / No Hand
04 - Serial Auto
05 - Serial Auto / No Hand
00 - Normal
82 (52)
31
UNITS
00 - Hertz
01 - RPM
02 - % Hz
03 - /SEC
04 - /MIN
05 - /HR
06 - None
07 - %
08 - PSI
09 - FPM
10 - CFM
11 - GPM
12 - IN
13 - FT
14 - /SEC
15 - /MIN
16 - /HR
17 - F
18 - C
19 - MPM
00 - Hertz
83 (53)
32
HZ MULT
10 - 65000 (.10 - 650.00)
100 (1.00)
2
84 (54)
33
UNITS DP
00 - XXXXX
01 - XXX.X
02 - XX.XX
03 - X.XXX
04 - .XXXX
00 - XXXXX
85 (55)
34
LOAD MLT
95 - 139 (95 - 139%)
100 (100%)
86 (56)
35
CONTRAST
00 - Low
01 - Medium
02 - High
02 - High
90 (5A)
39
TB5 MIN
0 - 36000 (.00 - 360.00 Hz)
0 (.00 Hz)
2
91 (5B)
40
TB5 MAX
0 - 36000 (.00 - 360.00 Hz)
0 (.00 Hz)
2
93 (5D)
42
TB10A OUT
00 - None
01 - 0 - 10 VDC
02 - 2 - 10 VDC
00 - None
94 (5E)
43
@TB10A
300 - 36000 (3.00 - 360.00 Hz)
6000 (60.00 Hz)
2
1
= Drive's programming parameter number;
2