Place the two stabilizing bars on the ground, and remove the bars.
Step 3. Remove the four screws that secure each of the outriggers, and remove the outriggers.
Figure 151. Removing the outriggers
Install the outriggers
Watch the procedure.
A video of this procedure is available from the following links:
• YouTube:
https://www.youtube.com/playlist?list=PLYV5R7hVcs-DOG7dnH9Zxy67Q3dez4ZsM
• Youku:
https://list.youku.com/albumlist/show/id_59715555
Procedure
Step 1. Extend each of the four leveling pads in turns until they firmly contact the floor and support the rack
cabinet. Make sure the cabinet is balanced by gently pushing the cabinet. If it tilts, adjust the length
of the leveling pads until the cabinet is well balanced.
.
Hardware removal, installation and reversion
135