ASHRAE class compliance information
Your server complies with ASHRAE class A2, A3 and A4 specifications. System performance may be
impacted when operating temperature is outside ASHRAE A2, A3 or A4 specifications. The restrictions to
ASHRAE A2 (10-35°C) support are as follows:
Server
status
Environment requirements
Operating
Ambient temperature
:
• ASHRAE class A2: 10–35°C (50–95°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 300 m (984 ft) of altitude increase.
• ASHRAE class A3: 5–40°C (41–104°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 175 m (574 ft) of altitude increase.
• ASHRAE class A4: 5–45°C (41–113°F); when the altitude exceeds 900 m (2953 ft), the maximum
ambient temperature value decreases by 1°C (1.8°F) with every 125 m (410 ft) of altitude increase.
Maximum altitude
: 3050 m (10 000 ft)
Relative humidity (non-condensing)
:
• ASHRAE class A2: 8%–80%; maximum dew point: 21°C (70°F)
• ASHRAE class A3: 8%–85%; maximum dew point: 24°C (75°F)
• ASHRAE class A4: 8%–90%; maximum dew point: 24°C (75°F)
Server off
Ambient temperature
:
5–45°C (41–113°F)
Shipping or
storage
Ambient temperature
:
-40–60°C (-40–140°F)
Maximum altitude
: 3050 m (10 000 ft)
Relative humidity (non-condensing)
: 8%–90%
Attention:
Airborne particulates and reactive gases acting alone or in combination with other environmental
factors such as humidity or temperature might pose a risk to the server. For information about the limits for
particulates and gases, see “Particulate contamination” on page 445.
Notes:
The restrictions to ASHRAE A2 (10-35°C) support are as follows:
• Mellanox ConnectX-6 adapters with Active Optical Cables (AOCs), ambient temperature cannot exceed
30°C
• With 8x 3.5-inch or 8x 2.5-inch or 16x 2.5-inch front drive bays + double-wide GPUs, ambient temperature
cannot exceed 30°C
• With 8x 3.5-inch or 16x 2.5-inch front drive bays + NVIDIA T4 GPU, ambient temperature cannot exceed
30°C
To comply with ASHRAE A3 (5-40°C) and A4 (5-45°C) specifications, the server models must meet the
following hardware configuration requirements:
• No Mellanox ConnectX-6 adapters
• No Broadcom 57454 10GBASE-T 4-port OCP Ethernet Adapter, 4XC7A08240
• No GPUs
446
ThinkSystem SR665 Maintenance Manual
Summary of Contents for 7D2V
Page 1: ...ThinkSystem SR665 Maintenance Manual Machine Types 7D2V and 7D2W ...
Page 6: ...iv ThinkSystem SR665 Maintenance Manual ...
Page 10: ...viii ThinkSystem SR665 Maintenance Manual ...
Page 66: ...56 ThinkSystem SR665 Maintenance Manual ...
Page 82: ...Figure 25 Cable routing for configuration 4 72 ThinkSystem SR665 Maintenance Manual ...
Page 123: ...Figure 40 Cable routing for configuration 1 Chapter 3 Internal cable routing 113 ...
Page 126: ...Figure 42 Cable routing for configuration 2 116 ThinkSystem SR665 Maintenance Manual ...
Page 131: ...Figure 45 Cable routing for configuration 6 Chapter 3 Internal cable routing 121 ...
Page 133: ...Chapter 3 Internal cable routing 123 ...
Page 148: ...138 ThinkSystem SR665 Maintenance Manual ...
Page 167: ...Chapter 4 Hardware replacement procedures 157 ...
Page 237: ...Chapter 4 Hardware replacement procedures 227 ...
Page 299: ...Chapter 4 Hardware replacement procedures 289 ...
Page 300: ...On the 2 5 inch middle drive cage 290 ThinkSystem SR665 Maintenance Manual ...
Page 339: ...Chapter 4 Hardware replacement procedures 329 ...
Page 364: ...354 ThinkSystem SR665 Maintenance Manual ...
Page 408: ...398 ThinkSystem SR665 Maintenance Manual ...
Page 431: ...5 Reseat the failing device 6 Replace the failing device Chapter 5 Problem determination 421 ...
Page 444: ...434 ThinkSystem SR665 Maintenance Manual ...
Page 445: ... Copyright Lenovo 2019 435 ...
Page 448: ...438 ThinkSystem SR665 Maintenance Manual ...
Page 449: ... Copyright Lenovo 2019 439 ...
Page 452: ...442 ThinkSystem SR665 Maintenance Manual ...
Page 464: ...454 ThinkSystem SR665 Maintenance Manual ...
Page 465: ......
Page 466: ......