Page 13
ELECTRICAL/ELECTRIC HEAT DATA
10 TON
10 TON STANDARD EFFICIENCY
ZHA120S4
1
Voltage - 60hz
208/230V - 3 Ph
460V - 3 Ph
575V - 3 Ph
Compressor 1
Rated Load Amps
15.6
7.8
5.8
Locked Rotor Amps
110
52
38.9
Compressor 2
Rated Load Amps
15.6
7.8
5.8
Locked Rotor Amps
110
52
38.9
Outdoor Fan
Motors (2)
Full Load Amps
3
1.5
1.2
(total)
(6)
(3)
(2.4)
Power Exhaust
(2) 0.5 HP
Full Load Amps
3
1.5
1.2
(total)
(6)
(3)
(2.4)
Indoor Blower
Motor
Horsepower
2
3
5
2
3
5
2
3
5
Full Load Amps
7.5
10.5
16.7
3.4
4.8
7.6
2.7
3.9
6.1
2
Maximum
Overcurrent
Protection
Unit Only
60
60
70
30
30
35
20
25
25
With (2) 0.5 HP
Power Exhaust
70
70
80
30
35
35
25
25
30
3
Minimum
Circuit
Ampacity
Unit Only
49
52
59
24
26
29
19
20
22
With (2) 0.5 HP
Power Exhaust
55
58
65
27
29
32
21
22
25
ELECTRIC HEAT DATA
Electric Heat Voltage
208V 240V 208V 240V 208V 240V 480V 480V 480V 600V 600V 600V
2
Maximum
Overcurrent
Protection
Unit+
Electric Heat
15 kW
90
100
100
100
100
110
50
50
60
40
40
40
22.5 kW
110
125
125
125
125
150
60
60
70
50
50
50
30 kW
150
150
150
150
150
150
70
80
80
60
60
60
45 kW
175
200
175
200
200
200
100
100
100
80
80
80
60 kW
175
200
200
200
200
225
100
100
110
80
80
80
3
Minimum
Circuit
Ampacity
Unit+
Electric Heat
15 kW
88
94
91
97
98
104
47
48
51
37
38
40
22.5 kW
108
117
111
120
117
126
58
60
62
46
47
49
30 kW
127
139
130
142
137
149
70
71
74
55
56
58
45 kW
166
184
169
188
176
194
92
94
96
73
74
76
60 kW
174
193
177
197
184
203
97
98
101
76
78
80
2
Maximum
Overcurrent
Protection
Unit+
Electric Heat
and (2) 0.5 HP
Power Exhaust
15 kW
100
100
100
110
110
110
50
60
60
40
40
45
22.5 kW
125
125
125
150
125
150
70
70
70
50
50
60
30 kW
150
150
150
150
150
175
80
80
80
60
60
70
45 kW
175
200
175
200
200
200
100
100
100
80
80
80
60 kW
200
200
200
225
200
225
100
110
110
80
80
90
3
Minimum
Circuit
Ampacity
Unit+
Electric Heat
and (2) 0.5 HP
Power Exhaust
15 kW
94
100
97
103
104
110
50
51
54
39
40
43
22.5 kW
114
123
117
126
123
132
61
63
65
48
49
52
30 kW
133
145
136
148
143
155
73
74
77
57
58
61
45 kW
172
190
175
194
182
200
95
97
99
75
76
79
60 kW
180
199
183
203
190
209
100
101
104
79
80
82
ELECTRIC HEAT ACCESSORIES
Unit Fuse Block
Unit Only
11M12 11M12 11M12 11M12 11M12 11M12 11M10 11M10 11M11 11M09 11M09 11M10
Unit + Power Exhaust
11M12 11M12 11M12 11M12 11M13 11M13 11M11 11M11 11M11 11M09 11M10 11M10
NOTE - All units have a minimum Short Circuit Current Rating (SCCR) of 5000 amps.
1
Extremes of operating range are plus and minus 10% of line voltage.
2
HACR type breaker or fuse.
3