background image

Page 4

STEP 2 -- REFRIGERANT PIPING -- New or
Existing Line Set and Indoor Coil 

F

lush existing line set per industry standards. For

more information concerning flushing procedures,
refer to the XC25 Installation and Service Procedures
available on DaveNet. 

CAUTION - 

DO NOT attempt to

flush and re-use existing line sets or indoor coil when
the system contains

 

contaminants (i.e., compressor

burn out).

IMPORTANT !

If this unit is being matched with an approved line
set or indoor unit coil that was previously charged
with mineral oil, or if it is being matched with a coil
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa­
tion. Take care to empty all existing traps. Polyol es­
ter (POE) oils are used in Lennox units charged with
HFC-410A refrigerant. Residual mineral oil can act
as an insulator, preventing proper heat transfer. It
can also clog the expansion device and reduce sys­
tem performance and capacity.
Failure to properly flush the system per the XC25
Installation and Service Procedures will void the
warranty.

WARNING

Polyol ester (POE) oils used with HFC-410A
refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
as much as possible. DO NOT remove line set caps
or service valve stub caps until you are ready to make
connections.

WARNING

Refrigerant can be harmful if it is inhaled. Refrigerant
must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
or death.

WARNING

Fire, Explosion and Personal Safety Haz­
ard. Failure to follow this warning could re­
sult in damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause fire
and/or an explosion, that could result in
property damage, personal injury or death.

WARNING

When using a high pressure gas
such as nitrogen to pressurize a
refrigeration or air conditioning
system, use a regulator that can
control the pressure down to 1 or 2
psig (6.9 to 13.8 kPa).

IMPORTANT !

Some scroll compressors have an internal vacuum
protector that will unload scrolls when suction pres­
sure goes below 20 psig. A hissing sound will be
heard when the compressor is running unloaded.
Protector will reset when low pressure in system is
raised above 40 psig. DO NOT REPLACE COM­
PRESSOR.

IMPORTANT !

If unit is equipped with a crankcase heater, and outdoor
ambient temperature is below 60°F, unit should be ener­
gized 24 hours before start­up to prevent compressor
damage as a result of slugging.

The XC25 is a variable capacity cooling and heat pump
system utilizing variable speed compressor technology.
With the variable speed compressor and variable pumping
capacity, additional consideration must be given to refri­
gerant piping sizing and application. The guidelines below
are to be used exclusively for the XC25 systems.

COOLING SYSTEM (HFC­410A)

S

Total equivalent length equals 180 feet (piping and all
fittings included).

NOTE — Length is general guide. Lengths may be more or
less, depending on remaining system design factors.

S

Maximum linear (actual) length = 150 feet.

S

Maximum linear liquid lift = 60 feet.

NOTE — 

Maximum lifts are dependent on total length,

number of elbows, etc

.

 that contribute to total pressure

drop.

S

Maximum length vapor riser equals 60 feet.

S

Up to 50 Linear Feet

: Use rated line sizes listed in

table 1.

S

Between 51 ­ 150 Linear Feet

: Crankcase heater and

non­bleed port TXV factory installed. No additional
components required. Vertical vapor riser must be
sized to the vapor riser listed in the table 2 on systems
with line sets longer than 51 feet. Use tables 2 and 3
to determine the correct liquid and vapor line sizes.

S

Over 150 Linear Feet

: not recommended.

S

Additional oil is not required for systems with line
lengths up to 150 feet.

SUCTION TRAPS

For systems with the outdoor unit 5 ­ 60 feet above the in­
door unit, one trap must be installed at the bottom of the
suction riser

.

Summary of Contents for XC25 Series

Page 1: ...ATION INSTRUCTIONS Dave Lennox Signature Collection XC25 System AIR CONDITIONERS 507004 01 6 14 2013 Supersedes 6 2013 PACKING LIST OUTDOOR UNIT WARRANTY CARD GROMMETS 2 BUSHING 1 RAST 6 PIN CONNECTOR 1 WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installation and service must be performed by a licensed HVAC p...

Page 2: ... WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTENERS AS SLAB SIDE MOUNTING IMPORTANT To help stabilize an outdoor unit some installations may ...

Page 3: ...ing this unit carefully stow all removed panels so that the panels will not cause injury to personnel objects or nearby structures Also take care to store panels where they will not be subject to damage e g being bent or scratched While handling or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged UNIT DIMENSIONS INCHES MM 4 5 8...

Page 4: ...gas such as nitrogen to pressurize a refrigeration or air conditioning system use a regulator that can control the pressure down to 1 or 2 psig 6 9 to 13 8 kPa IMPORTANT Some scroll compressors have an internal vacuum protector that will unload scrolls when suction pres sure goes below 20 psig A hissing sound will be heard when the compressor is running unloaded Protector will reset when low press...

Page 5: ...65 40 40 feet 12 2 m 89J61 L15 65 50 50 feet 15 2 m 89J62 XC25 060 230 XX 3 8 10 mm 1 1 8 29 mm Field fabricated Applicable to all minor revision numbers unless otherwise specified Some applications may required a field provided 1 1 8 to 7 8 adapter Table 2 XC25 Line Set Guidelines Between 51 150 Linear Length Model Maximum Total Equivalent Length ft Maximum Linear actual Length ft Maximum Vapor R...

Page 6: ...he two Teflon rings 8 Use a field provided fitting to temporarily reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR ...

Page 7: ...ervice port nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines square free from nicks or dents and debur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction vapor and liquid line service...

Page 8: ...ated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction vapor valve stem port See steps 3A 3B and 3C on previous page and below for manifold gauge setup 5 SUCTION VAPOR LINE WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE LIQUID LINE WATER SATURATED CLOTHS WATER SATURATED CLO...

Page 9: ...LATION 1 2 3 4 5 6 7 8 9 10 11 12 1 8 Turn 1 Remove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure below 2 Remove the field provided fitting that temporarily reconnected the liquid line to the indoor unit s distributor assembly INDOOR EXPANSION VALVE INSTALLATION 3 Install one of the provi...

Page 10: ...the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the line set and indoor unit Weigh in a trace amount of HFC 410A A trace amount is a maximum of two ounces 57 g refriger ant or three pounds 31 kPa pressure Close the valve on the HFC 410A cylinder ...

Page 11: ...p and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following S Close manifold gauge valves S Shut of...

Page 12: ...ake care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the unit the control and the technician at the same electrostatic potential Touch hand and all tools on an unpainted unit surface before performing any service procedure to neutralize electrostatic charge Refer to the unit nam...

Page 13: ...inals PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMPER PLACED ACROSS THE TWO PUMP DOWN PINS TO DEACTIVATE REMOVE JUMPER FIGURE 10 ...

Page 14: ... nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is located side panel of the control box Connect conduit to the ...

Page 15: ...ater i e sprinkler systems soakers waste water etc will corrode the surface of steel and aluminum parts diminish performance and affect longevity of the unit Outdoor Coil The outdoor unit must be properly maintained to ensure its proper operation S Please contact your dealer to schedule proper inspec tion and maintenance for your equipment S Make sure no obstructions restrict airflow to the outdoo...

Page 16: ...ture Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach temperatures Subcooling A B SUBCOOLING Saturated Condensing Temperature A minus Liquid Line Temperature B Approach A B APPROAC...

Reviews: