20
VVCA048H4, VVCA054H4
Description
Input
Blower
Motor
Full
Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
5
Single Point
Power Source
Blower Speed
Volt
kW
1
Btuh
Ckt 1 Ckt 2 Ckt 1 Ckt 2
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Low
Medium High
5 kW
V8EH0050P-1P
(
13P59
)
208
3.8
12,800
4.2
28.3
- - -
4
30
- - -
- - -
- - -
•
•
•
220
4.2
14,300
4.2
29.3
- - -
4
30
- - -
- - -
- - -
•
•
•
230
4.6
15,700
4.2
30.3
- - -
35
- - -
- - -
- - -
•
•
•
240
5.0
17,100
4.2
31.3
- - -
35
- - -
- - -
- - -
•
•
•
7.5 kW
V8EH0080P-1P
(
13P63
)
208
5.6
19,200
4.2
39.3
- - -
4
40
- - -
- - -
- - -
•
•
•
220
6.3
21,500
4.2
41.3
- - -
45
- - -
- - -
- - -
•
•
•
230
6.9
23,500
4.2
42.3
- - -
45
- - -
- - -
- - -
•
•
•
240
7.5
25,600
4.2
44.3
- - -
45
- - -
- - -
- - -
•
•
•
10 kW
V8EH0100P-1P
(
13P64
)
208
7.5
25,600
4.2
50.3
- - -
60
- - -
- - -
- - -
•
•
•
220
8.4
28,700
4.2
53.3
- - -
60
- - -
- - -
- - -
•
•
•
230
9.2
31,400
4.2
55.3
- - -
60
- - -
- - -
- - -
•
•
•
240
10.0
34,100
4.2
57.3
- - -
60
- - -
- - -
- - -
•
•
•
15 kW
V8EH0150P-1P
(
13P75
)
208
11.3
38,400
4.2
50.3
23
60
4
25
73.3
80
6
- - -
•
•
220
12.6
43,000
4.2
53.3
24
60
4
25
77.3
80
6
- - -
•
•
230
13.8
47,000
4.2
55.3
25
60
4
25
80.3
90
6
- - -
•
•
240
15.0
51,000
4.2
57.3
26
60
30
83.3
90
6
- - -
•
•
20 kW
V8EH0200P-1P
(
13P76
)
208
15.0
51,200
4.2
50.3
45
60
4
50
95.3
100
6
- - -
•
•
220
16.8
57,300
4.2
53.3
48
60
4
50
101.3
110
6
- - -
•
•
230
18.4
62,700
4.2
55.3
50
60
4
50
105.3
110
6
- - -
•
•
240
20.0
68,200
4.2
57.3
52
60
60
109.3
110
6
- - -
•
•
ELECTRIC HEAT DATA
036-054
VVCA036H4
Description
Input
Blower Motor
Full Load
Amps
2
Minimum
Circuit
Ampacity
3
Maximum
Overcurrent
Protection
Blower Speed
Volt
kW
1
Btuh
Low
Medium
High
5 kW
V8EH0050P-1P (
13P59
) 208
3.8
12,800
4.2
28.3
4
30
•
•
•
220
4.2
14,300
4.2
29.3
4
30
•
•
•
230
4.6
15,700
4.2
30.3
35
•
•
•
240
5.0
17,100
4.2
31.3
35
•
•
•
7.5 kW
V8EH0080P-1P (
13P63
) 208
5.6
19,200
4.2
39.3
4
40
•
•
•
220
6.3
21,500
4.2
41.3
45
•
•
•
230
6.9
23,500
4.2
42.3
45
•
•
•
240
7.5
25,600
4.2
44.3
45
•
•
•
10 kW
V8EH0100P-1P (
13P64
) 208
7.5
25,600
4.2
50.3
60
6
- - -
•
•
220
8.4
28,700
4.2
53.3
60
6
- - -
•
•
230
9.2
31,400
4.2
55.3
60
6
- - -
•
•
240
10.0
34,100
4.2
57.3
60
6
- - -
•
•
REPLACEMENT CIRCUIT BREAKERS
Voltage
Description
Catalog No.
208/240V - 1
Phase
25 amp, 2 pole
41K13
30 amp, 2 pole
17K70
40 amp, 2 pole
49K14
50 amp, 2 pole
41K12
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower
Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat
capacity.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse
and disconnect size requirements. Use wires suitable for at least 167°F.
3
HACR type breaker or fuse.
4
Bold text indicates that the circuit breaker on CB” circuit breaker models must
be replaced with size noted. See Table on page <?>.
5
Single point power source breaker for unit with 15 and 20 kW electric heat is
not furnished and must be field provided.
6
Do not operate fan on low speed when V8EH Electric Heat Kit is used with
VVCA air handler.