DC Inverter Multi VRF System
8
Unit:mm
Model
A
B
C
D
E
VEC027N432U
VEC034N432U
VEC042N432U
980
360
790
650
395
4.2 Connection Pipe
4.2.1 Schematic Diagram of Piping Connection
Fig.4.2.1.1
4.2.2 Allowable Length and Height Difference of Connection Pipe
Y type branch joint is adopted to connect indoor and outdoor units. Connecting method is shown
in the figure below:
NOTE!
Equivalent length of one Y-type branch is 0.5m.
Piping parameters of
VEC027N432U
,
VEC034N432U
,
VEC042N432U
.
Allowable
value
Fitting pipe
Total length (actual length) of fitting pipe
250m
L1+L2+L3+a+b+c+d
Length of farthest fitting pipe (m)
Actual length
100m
L1+L2+L3+d
Equivalent length
120m
From the 1
st
branch to the farthest indoor pipe
40m
L2+L3+d