Multi Variable Air Conditioners Compact Cassette Type Indoor Unit 

21 

6.3 Maintenance after the Seasonal Use 

(1)  Set the unit in fan mode for half a day in a sunny day to dry the inner part of unit. 
(2)  When the unit won’t be used for a long time, please cut off power supply for energy saving; 

the characters on the wired controller screen will disappear after cutting off the power 
supply. 

7 Table of Error Codes for Indoor Unit 

Error 

Code 

Content 

Error 

Code 

Content 

Error 

Code 

Content 

L0 

Indoor Unit Error 

LA 

Indoor Units Incompatibility 

Error 

d9 

Jumper Cap Error 

L1 

Indoor Fan Protection 

LH 

Low Air Quanlity Warning 

dA 

Indoor Unit Network 

Address Error 

L2 

E-heater Protection 

LC 

ODU-IDU Incompatibility 

Error 

dH 

Wired Controller PCB 

Error 

L3 

Water Full Protection 

d1 

Indoor Unit PCB Error 

dC 

Capacity DIP Switch 

Setting Error. 

L4 

Wired Controller Power 

Supply Error 

d3 

Ambient Temperature 

Sensor Error 

dL 

Indoor Unit CO

2

 Sensor 

Error 

L5 

Freeze Protection 

d4 

Inlet Pipe Temperature 

Sensor Error 

dE 

Capacity DIP Switch 

Setting Error. 

L7 

No Master Indoor Unit 

Error 

d6 

Outlet Pipe Temperature 

Sensor Error 

db 

Special Code: Field 

Debugging Code 

L8 

Power Insufficiency 

Protection 

d7 

Humidity Sensor Error 

C0 

Communication Error 

L9 

Quantity Of Group Control 

Indoor Units Setting Error 

d8 

Water Temperature Sensor 

Error 

AJ 

Filter Cleaning Reminder 

o1 

Low Bus bar Voltage of 

Indoor Unit 

o2 

High Bus bar Voltage of 

Indoor Unit 

o3 

IPM Module Protection of 

Indoor Unit 

o4 

Failure Startup of Indoor 

Unit 

o5 

Overcurrent Protection of 

Indoor Unit 

o6 

Current Detection Circuit 

Malfunction of Indoor 

Unit 

o7 

Desynchronizing 

Protection of Indoor Unit 

o8 

Communication 

Malfunction of Indoor Unit’s 

Drive 

o9 

Communication 

Malfunction of Main 

Mater of Indoor Unit 

oA 

High Temperature of 

Indoor Unit’s Module 

ob 

Malfunction of 

Temperature Sensor of 

Indoor Unit’s Module 

oC 

Charging Circuit 

Malfunction of Indoor 

Unit 

o0 

Other Drive Malfunction 

db 

Special Code: Field Debugging Code 

 

Summary of Contents for VRF VE8C005C432P

Page 1: ...l Compact 8 Way Cassette Thank you for selecting LENNOX air conditioners Please read this manual carefully before operation and keep it for further reference VE8C005C432P VE8C007C432P VE8C009C432P VE8...

Page 2: ......

Page 3: ...te normally please contact our service center as soon as possible and provide the following information 1 Content on the nameplate model number cooling capacity production code ex factory date 2 Malfu...

Page 4: ...turer 3 After verification the defect of product is directly caused by corrosive gas 4 After verification defects are due to improper operation during transportation of product 5 Operate repair mainta...

Page 5: ...Testing 9 4 4 Locking Joint Installation 13 4 5 Panel Installation 14 4 6 Installation of Wired Controller 16 5 Wiring Work 16 5 1 Connection of Wire and Patch Board Terminal 16 5 2 Power Cord Connect...

Page 6: ...te normally 13 When installation is finished please check whether the drainage pipes pipelines and electric wires are connected correctly to avoid water leakage refrigerant leakage electric shock or f...

Page 7: ...on 2 1 Names of Key Components Fig 2 1 1 No 1 2 3 4 Name Drainage device Drainage Pipe Air flow flap Connection Pipe 2 2 Rated Working Condition Indoor Side Condition Outdoor Side Condition Dry Bulb T...

Page 8: ...ling off 12 Fastener 200mm 4 To fasten the sponge 13 Bolt with Washer 4 To fix the installation paperboard on the unit 14 Enswathement 2 Used for winding the pipe connecting the indoor and outdoor uni...

Page 9: ...t shall be installed in accordance with national standards or local regulations 2 Only qualified personnel can carry out installation work please contact with local dealer before installation 3 Make s...

Page 10: ...mmunication Wire between Indoor Unit and Indoor Unit or Outdoor Unit Fig 3 3 2 Material Type Total Length L m ft of Communication Cable between Indoor Unit and Indoor Outdoor Wire size mm2 AWG Materia...

Page 11: ...ture of 40 C 104 F 4 The circuit breaker specification in above sheet is based on ambient temperature of 40 C 104 F If the working condition is different please adjust it according to the specificatio...

Page 12: ...temporarily Assemble suspension bolt on the expansion bolt attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut and washer from upper and lower sides of the hange...

Page 13: ...screwed joint and then tighten the flaring nut with hand as shown in Fig 4 2 1 2 Use a torque wrench to tighten up the flaring nut until the wrench gives out a click sound Fig 4 2 1 Pipe diameter mm i...

Page 14: ...he following Fig 4 3 1 and arrange insulation to the drainage pipe Improper installation may lead to water leakage and damp the furniture and other things in the room 7 You can buy normal hard PVC pip...

Page 15: ...ected to vertical pipe in the same level please select the connection way as shown in following figure 1 Three way connection of drainage pipe joints Fig 4 3 3 2 Connection of downspout elbow Fig 4 3...

Page 16: ...e less than C as shown in Fig 4 3 7 Unit mm inch Fig 4 3 7 Unit mm inch Model A B C 225 8 7 8 975 38 3 8 925 36 7 16 11 During the installation distance from soft drain pipe to the gasket is C when th...

Page 17: ...p etc 2 In case of commissioning finished please energize the IDUs and switch to cooling or dry mode meanwhile the water pump operates you can check the draining through the drain socket 3 If communic...

Page 18: ...ed to be fixed through the side panel locking connector The fixing process is as follows 1 Remove the locking joint bracket from the side panel Fig 4 4 1 2 Attach the locking joint to the locking join...

Page 19: ...ion 1 Improper decorative panel installation could cause the following problems Fig 4 5 1 2 Ensure that it s clearance free between decoration panels and ceiling board after installation if not please...

Page 20: ...keep the mark and fittings on the same corner as shown in Fig 4 5 4 Fig 4 5 4 2 Adjust the position of panel to make the panel holes fix at the holes on the units 3 Fix the 4 screws at the two side of...

Page 21: ...y read the wiring diagram before carry out the wiring work incorrect wiring could cause malfunction or even damage the unit 3 The unit should be powered by independent circuit and specific socket 4 Th...

Page 22: ...terminal board 3 Insert the wire into the ring tongue terminal and tighten by crimping tool 4 Use the screwdriver for tightening the terminal Unit mm inch Fig 5 1 1 Fig 5 1 2 5 2 Power Cord Connection...

Page 23: ...shown in Fig 5 3 1 Fig 5 3 1 Fig 5 3 2 4 Fix the communication cable with clamp of electric box 5 For more reliable communication make sure connect the terminal resistor to the most downstream IDU of...

Page 24: ...2 2 Wired controller is connected to H1 H2 3 One indoor unit can connect two wired controllers that must be set as master one and slave one 4 One wired controller can control 16 indoor units in maximu...

Page 25: ...oth dipped in neutral detergent 6 Please contact after sales service staff if there is abnormal situation 6 1 Cleaning of Filter 1 Remove the filters from inlet of IDU Use a vacuum cleaner to remove d...

Page 26: ...rature Sensor Error dL Indoor Unit CO2 Sensor Error L5 Freeze Protection d4 Inlet Pipe Temperature Sensor Error dE Capacity DIP Switch Setting Error L7 No Master Indoor Unit Error d6 Outlet Pipe Tempe...

Page 27: ...t temperature is higher than 43 109 Poor cooling effect The filter is dirty or blocked Too heavy heat load of room e g too many people Door or windows is open Air inlet and outlet of IDU are blocked S...

Page 28: ...t us at 1 305 718 2901 lennoxglobalhvac lennoxintl com C 2020 Lennox Industries Inc For a complete list of the registered and common law trademarks owned by Lennox Industries Inc please visit www lenn...