Page 6
507994-01 11/19
6 (152)
36 (914)
12 (305)
30 (762)
LINE SET
CONNECTIONS
24 (610)
48 (1219)
MINIMUM CLEARANCE BETWEEN
TWO UNITS
CLEARANCE ON ALL SIDES — INCHES (MILLIMETERS)
ACCESS PANEL
MINIMUM CLEARANCE
ABOVE UNIT
NOTES:
Clearance to one of the other three
sides must be 36 inches (914mm).
Clearance to one of the remaining
two sides may be 12 inches
(305mm) and the final side may be
6 inches (152mm).
Figure 4. Installation Clearances
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees
(or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
DETAIL A
DETAIL B
DISCHARGE AIR
MOUNTING SLAB MUST SLOPE
AWAY FROM BUILDING.
GROUND LEVEL
STRUCTURE
Install unit away
from windows .
Two 90° elbows
installed in line set will
reduce line set vibration.
Figure 5. Placement, and Slab Mounting
New Unit Placement
See
Unit Dimensions
on page 2 for sizing mounting slab,
platforms or supports. Refer to figure 4 for mandatory
installation clearance requirements.
CAUTION
In order to avoid injury, take proper precaution when
lifting heavy objects.
POSITIONING CONSIDERATIONS
Consider the following when positioning the unit:
Some localities are adopting sound ordinances based
on the unit's sound level registered from the adjacent
property, not from the installation property. Install the
unit as far as possible from the property line.
When possible, do not install the unit directly outside
a window. Glass has a very high level of sound
transmission. For proper placement of unit in relation
to a window see the provided illustration in figure 5,
detail A.