background image

Page 7

Revised 05−2009

TPA*S4

1

2

3

4

SUCTION

POCKET

SUCTION

ORBITING SCROLL

STATIONARY SCROLL

SUCTION

SUCTION

DISCHARGE

 POCKET

SUCTION

INTERMEDIATE PRESSURE

GAS

CRESCENT

SHAPED

GAS POCKET

HIGH PRESSURE GAS

FLANKS SEALED

BY CENTRIFUGAL

FORCE

MOVEMENT OF ORBIT

FIGURE 8

Make sure all power is disconnected before
beginning electrical service procedures.

DANGER

C − Outdoor Fan Motor B4

All units use single−phase PSC fan motors . In all units, the
condenser fan is controlled by the compressor
contactor (and defrost control during defrost cycles).
ELECTRICAL DATA tables in this manual show
specifications for condenser fans used in TPA*S4s.
Access to the condenser fan motor on all units is gained
by removing the seven screws securing the fan
assembly. See figure 9. The outdoor fan motor is
removed from the fan guard by removing the four nuts
found on the top panel. If outdoor fan motor must be
replaced, align fan hub flush with motor shaft. Drip loops
should be used in wiring when servicing motor.

FAN

CONDENSER FAN MOTOR

AND COMPRESSOR ACCESS

Remove (7) screws

REMOVE (7) SCREWS

SECURING FAN GUARD.

REMOVE FAN GUARD/FAN

ASSEMBLY.

FAN GUARD

WIRING

FIGURE 9

Remove (4) nuts

ALIGN FAN HUB

FLUSH WITH

MOTOR SHAFT

D − Reversing Valve L1 and Solenoid

A refrigerant reversing valve with electro−mechanical
solenoid is used to reverse refrigerant flow during unit
operation. The reversing valve requires no maintenance.
The only replaceable part is the solenoid. If the reversing
valve itself has failed, it must be replaced.

If replacement is necessary, access reversing valve by
removing the outdoor fan motor. Refer to figure 9.

E − Crankcase Heater HR1 and Optional

Thermostat S40

Crankcase heater HR1 prevents liquid from accumulating
in the compressor. HR1 is controlled by crankcase heater
thermostat S40, located on the liquid line. When liquid  line
temperature drops below 50° F, S40 closes energizing
HR1. S40 opens when liquid line temperature reaches 70°.

F − High Pressure Switch S4

S4 is a manual re−set switch located on the liquid line.
When liquid line pressure rises above the factory setting of
590 +  10 psi, the switch opens and shuts off the
compressor.

G − Low Pressure Switch S87

S87 is an auto−reset low pressure switch located on the
suction line. The switch shuts of the compressor when
suction pressure drops below the factory setting. The
switch is ignored during the first 90 seconds of compressor
start up, during defrost operation,90 seconds after defrost
operation and during test mode. The switch is factory set to
open at 25 + 5 psig and close at 40 + 5 psig. These settings
are not adjustable.

Summary of Contents for T?CLASS TPA S4

Page 1: ...allation adjustment alteration service or maintenance can cause personal injury loss of life or damage to property Installation and service must be performed by a licensed professional installer or eq...

Page 2: ...tdoor Fan Diameter in No of Blades 18 4 22 4 22 4 22 4 Motor hp 208 230V 1 5 460V 1 6 1 3 1 3 1 4 Cfm 2450 3890 3890 3830 Rpm 1100 1080 1085 830 Watts 190 400 375 330 Shipping Data lbs 1 package 180 2...

Page 3: ...harge sufficient for 15 ft length of refrigerant lines 2 HACR type circuit breaker or fuse 3 Refer to National or Canadian Electrical Code manual to determine wire fuse and disconnect size requirement...

Page 4: ...box See figure 3 24V THERMOSTAT TERMINAL STRIP FIGURE 3 W1 C L R O Y1 1 Compressor Contactor K1 The compressor is energized by a contactor located in the control box See figure 2 Three pole contactor...

Page 5: ...utes have passed If the jumper is not removed until after the additional 5 second period has elapsed the defrost will terminate and the test option will not function again until the jumper is removed...

Page 6: ...ESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 8 1 The centrifugal action of the orbiting scroll s...

Page 7: ...OTOR SHAFT D Reversing Valve L1 and Solenoid A refrigerant reversing valve with electro mechanical solenoid is used to reverse refrigerant flow during unit operation The reversing valve requires no ma...

Page 8: ...EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD DISTRIBUTOR INDOOR COIL TO HFC 410A DRUM FIGURE 11 TPA S4 HEATING CYCLE SHOWING MANIFOLD GAUGE CONNECTIONS OUTDOO...

Page 9: ...n adjustable wrench 2 Using service wrench and hex head extension 5 16 for vapor line and 3 16 for liquid line back the stem out counterclockwise until the valve stem just touches the retaining ring 3...

Page 10: ...es and within the system Regulator setting must not exceed 150 psig 1034 kpa Failure to use a regulator can cause equipment failure resulting in injury or death C Evacuating the System 1 Attach gauge...

Page 11: ...ough the outdoor coil to achieve pressures in the 200 250 psig 1379 1724 kPa range These higher pressures are necessary for checking the charge Block equal sections of air intake panels and move obstr...

Page 12: ...290 74 307 73 300 73 309 62 20 7 283 58 298 61 286 60 300 56 1 These are most popular match up pressures Indoor match up indoor air quality and indoor load cause pressures to vary 2 Temperature of th...

Page 13: ...23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 1...

Page 14: ...per 1 5m NOTE If line length is greater than 15 ft 4 6 m add this amount If line length is less than 15 ft 4 6 m subtract this amount Subcooling Charging Method Requirements these items are required f...

Page 15: ...temperature record in the LIQ space 7 Read the liquid line pressure then find its corresponding temperature in the temperature pressure table 13 and record it in the SAT space 8 Subtract LIQ temp fro...

Page 16: ...32 100 8 67 190 9 102 326 4 4 43 1 33 102 9 68 194 1 103 331 2 45 6 34 105 69 197 3 104 335 7 0 48 2 35 107 1 70 200 6 105 340 5 1 49 5 36 109 2 71 203 9 106 345 3 2 50 9 37 111 4 72 207 2 107 350 1 3...

Page 17: ...rgizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C de...

Page 18: ...valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C defrost switch thermost...

Reviews: