Page 19
SYSTEM MODULE LAYOUT (EXAMPLE)
Figure 17. System Module Layout
Wiring
Table 2 reflects the recommended wire sizing for the wiring
between the junction box at the beginning of the branch and
the solar disconnect.
The lengths are calculated for a 1.5% maximum voltage
drop. The values take into account the 6' of 14AWG wire
between the individual microinverters.
NOTE - For more detailed information refer to
Enphase -
Microinverter System Installation and Operation Manual.
Table 2. Maximum Wire Length — Feet (Meters)
Wire Size
(AWG)
Number of Solar Modules per Branch
Wire length maximum distance from solar modules to HVAC unit.
7
8
9
10
11
12
13
14
15
16
10
148
(45)
130
(40)
115
(35)
104
(32)
94
(29)
87
(27)
80
(24)
74
(23)
69
(21)
65
(20)
8
237
(72)
207
(63)
184
(56)
166
(51)
151
(46)
138
(42)
127
(39)
118
(36)
110
(34)
103
(31)
6
375
(114)
328
(100)
292
(89)
263
(80)
239
(73)
219
(67)
202
(62)
188
(57)
175
(53)
164
(50)