background image

1

PRODUCT RANGE

UNIT

V / Ph / 50 Hz

NOMINAL

 CAPACITY W

10.700

13.600

3,18

3,82

400 V - 3Ph

230 V - 3Ph

400 V - 3Ph

NOMINAL 

CONSUMPTION KW

230 V - 1Ph
230 V - 3Ph

230 V - 1Ph

SNE 2,8K

8.300

2,68

SNE 4K

SNE 3K

CONTENTS

• PRODUCT RANGE

• GENERAL DESCRIPTION
• 

SPECIFICATIONS

• ELECTRICAL CONNECTIONS

• FANS SPECIFICATIONS
• FUNCTION LIMITS

• 

TABLE OF CAPACITIES

• CONSUMPTION AND DROP WATER
• UNIT DIMENSIONS

• INSTALLATION

• 

MAINTENANCE OF THE UNIT

• 

OPTIONS

• POINTS TO KEEP IN MIND

• 

NOTES

PAGE

1

2
3

4

5
5

6

7
8

9

10
11

12

13-14

TABLE

Congratulations, you have made a wise choice the purchase of this product. This product 

has been designed, assembled and supplied in one of our world class manufacturing 

facilities and we feel that it will meet your expectations.

Summary of Contents for SNE 2

Page 1: ...L CONNECTIONS FANS SPECIFICATIONS FUNCTION LIMITS TABLE OF CAPACITIES CONSUMPTION AND DROP WATER UNIT DIMENSIONS INSTALLATION MAINTENANCE OF THE UNIT OPTIONS POINTS TO KEEP IN MIND NOTES PAGE 1 2 3 4...

Page 2: ...egulating water flow Discharge plenum Admission plenum Digital thermostat programmable COMPRESSOR CONDENSER AIR FILTER COOLING CIRCUIT HEAT EXCHANGER CABINET FAN OPTIONS Made of welded dehumidifying c...

Page 3: ...d water pressure drop Hydraulic connections Sound level LP 2 Dimensions Kw l h W KPa dB A mm H Large W mm mm SNE 4K SNE 3K Air flow max min Pa Available static power 1 Net weight Kg 13 600 3 82 SNE 4K...

Page 4: ...2 1 2 2 6 X 1 5mm 2 6 X 1 5mm 2 6 X 1 5mm 2 6 X 1 5mm 2 6 X 1 5mm 2 6 X 1 5mm Power supply Thermostat connections 1 2 2 3 X 4mm 2 4 X 6mm 2 5 X 4mm 2 3 X 4mm 2 4 X 4mm 2 5 X 2 5mm MODEL VOLTAGE 50Hz...

Page 5: ...1075 950 1800 1650 1550 1425 975 1300 1150 80 100 120 140 0 20 40 60 1840 1700 1575 1375 SNE 3K 1275 2000 1850 1700 1550 1375 1100 2050 1925 1775 1625 1450 1250 80 100 120 140 0 20 40 60 1840 1700 15...

Page 6: ...32 C DB 23 C WB TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE TOTAL SENSIBLE 7 84 5 68 8 50 6 09 9 21 6 49 9 98 6 53 10 81 6 90 30 C 9 80 7 13 10 65 7 66 11 58 8 18 12 58 8 24 13 66 8 74...

Page 7: ...UNIT For different air inlet temperature multiply the consumption by the coefficent of this table Normally the water condense is used across a cooling tower with water temperature around 30 C and wate...

Page 8: ...or an easy access depending on the installation of the unit Factory position of the electrical box Option position of the electrical box To change by the installer DETAIL A 5 6 9 DETAIL A 1 2 3 4 5 6...

Page 9: ...sumption for each unit All installation must be carried out by qualified personnel Make sure that the unit is completely disconnected from the power supply before carrying out any type of work on the...

Page 10: ...r three phase and cooling elements of security like high and low pressostat pressure with electrical rearm If limits of function of the unit is out of conditions of work some protections will be displ...

Page 11: ...ir Use the admission plenum if you are going to use duct of aspiration air or hot water coil The superior part is detachable to access and clean air filter of the unit PLENUM This optional kit include...

Page 12: ...SOSTATIC VALVES Connect a manometer of high pressure 30 bar near the refrigerating circuit of the unit Turn over the vastage in the head of the valve right the valve open left the valve close regulati...

Page 13: ...uideliness on how to avoid accidents and serious damage before commissioning the equipment and during its operation and how to ensure smooth and fault free operation Read the operating instructions ca...

Page 14: ...14 NOTAS...

Page 15: ...SNE K OPERATION SERVICE AND INSTALLATION MANUAL...

Page 16: ...4209790 fax 496942097940 e mail info lennoxdeutschland com LENNOXBENELUXB V t l 31332471800 fax 31332459220 e mail info lennoxbenelux com LENNOXPOLSKASPzo o t l 48228322661 fax 48228322662 e mail lenn...

Reviews: