Page 8
BLOWER DATA
SLP99DF110XV60C BLOWER PERFORMANCE (less filter)
HEATING BLOWER PERFORMANCE - 0 through 0.8 in. w.g. External Static Pressure Range
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
811
906
1096
1286
1475
1665
1855
2045
Increase (+7.5%) Heat CFM
744
835
1017
1199
1380
1562
1744
1926
Default Heat CFM
677
764
938
1112
1285
1459
1633
1807
Decrease (-7.5% ) Heat CFM
626
707
869
1031
1193
1355
1517
1679
Decrease (-15% ) Heat CFM
575
650
800
950
1101
1251
1401
1551
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single-stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times.
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages.
Cool Mode Available (Cooling Blower Performance Table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28% and 38% (DIP switch selectable) of the same second-stage COOL speed position minimum 250 cfm.
Lennox iHarmony
®
Zoning System Applications - Minimum blower speed is 450 cfm.
COOLING BLOWER PERFORMANCE - 0 through 1.0 in. w.g. External Static Pressure Range
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
1090
1260
1395
1580
1580
1790
1990
2180
Default Cool CFM
965
1125
1285
1440
1440
1625
1845
2000
Decrease (-10%) Cool CFM
860
1030
1125
1270
1270
1470
1655
1845
SLP99DF110XV60C BLOWER MOTOR WATTS - COOLING
Blower Speed
Options
Motor Watts @ Various External Static Pressures - in. wg.
First Stage
Second Stage
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Increase (+10%) Cool CFM
Low 71
99 147 166 202 240 271 302 337 248 280 333 374 429 469 511 548 594 619 677
Medium-Low 127 159 198 225 256 301 325 365 390 409 427 496 531 587 632 665 721 742 781 805
Medium-High 162 204 242 287 316 371 408 446 487 563 589 651 703 755 808 860 888 932 970 1007
High 243 280 333 374 429 469 511 548 594 866 850 915 963 1020 1056 1091 1127 1141 1136 1131
Default Cool CFM
Low 57
88 117 140 165 196 232 259 283 167 214 244 291 331 380 405 467 497 539 583
Medium-Low 77 112 147 172 209 250 283 317 345 275 321 348 418 447 505 546 597 632 668 716
Medium-High 122 154 199 230 268 300 331 373 411 461 493 547 572 628 666 703 745 777 819 860
High 167 214 244 291 331 380 405 467 497 601 626 688 730 787 823 880 924 963 994 1011
Decrease (-10%) Cool CFM
Low 44
67
99 115 144 167 197 215 245 126 165 201 232 262 305 334 373 417 451 479
Medium-Low 66
97 123 153 186 216 247 275 303 187 219 272 308 360 391 432 479 514 559 588
Medium-High 77 112 147 172 209 250 283 317 345 308 341 390 430 490 528 569 617 640 691 724
High 127 165 201 232 262 305 334 373 417 461 493 547 572 628 666 703 745 777 819 860