Page 44
BLOWER DATA
SL280UH090V60C BLOWER PERFORMANCE (less filter)
SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range
HEATING
1
Heating Speed
DIP Switch
Settings
First Stage Heating Speed - cfm
Second Stage Heating Speed - cfm
+24%
1360
1495
+18%
1290
1420
+12%
1225
1350
+6%
1160
1275
Factory Default
1095
1205
–6%
1030
1130
–12%
965
1060
–18%
900
990
COOLING
1
Cooling Speed
DIP Switch
Settings
First Stage Cooling Speed - cfm
Second Stage Cooling Speed - cfm
Low
Medium-Low Medium-High
2
High
Low
Medium-Low Medium-High
2
High
+
1050
1190
1380
1615
1515
1715
1930
2240
Factory Default
970
1090
1245
1485
1380
1560
1755
2070
–
880
985
1095
1285
1215
1400
1580
1830
1
Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch
Settings.
2
Factory default setting.
NOTES - The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage HEAT.
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm.
Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 480 cfm.