background image

Page 11

Removing the Bottom Panel

Remove the two screws that secure the bottom cap to the 

furnace. Pivot the bottom cap down to release the bottom 

panel. Once the bottom panel has been removed, reinstall 

the bottom cap. See figure 11.

Removing the Bottom Panel

Screw

Bottom Panel

Bottom Cap

Figure 11 

Horizontal Application

Installation Clearances

Top

Bottom

Left

End

Right

End

AIR 

FLOW

Vent Connector

Type

Type C

Type B1

Top

0

0

*Front

2-1/4 in. (57 mm)**

2-14 in. (57 mm)

Back

0

0

Ends

2 in. (51 mm)

2 in. (51 mm)

Vent

6 in. (152 mm)

1 in. (25 mm)

Floor

0

0

*Front clearance in alcove installation must be 24 in. (610 mm).

Maintain a minimum of 24 in. (610 mm) for front service access.

** 3-1/4 in. if single wall vent pipe is used.

For installations on a combustible floor, do not install the furnace

directly on carpeting, tile or other combustible materials other

than wood flooring.

FIGURE 12

Horizontal Applications

The SL280UHV furnace can be installed in horizontal ap-

plications. Order kit number 51W10 (or use equivalent) 

from Lennox.
Allow for clearances to combustible materials as indicated 

on the unit nameplate. Minimum clearances for closet or 

alcove installations are shown in figure 12.

This furnace may be installed in either an attic or a crawl-

space. Either suspend the furnace from roof rafters or 

floor joists, as shown in figure 13, or install the furnace on 

a platform, as shown in figure 14.

Typical Horizontal Application

Unit Suspended in Attic or Crawlspace

Bracket

Bottom Cap

Metal Strap

3/16 inch

Air Flow

FIGURE 13

NOTE - Heavy-gauge perforated sheet metal straps may 

be  used  to  suspend  the  unit  from  roof  rafters  or  ceiling 

joists. When straps are used to suspend the unit in this 

way,  support  must  be  provided  for  both  the  ends.  The 

straps must not interfere with the plenum or exhaust pip-

ing installation. 

Cooling coils and supply and return air 

plenums must be supported separately.
NOTE - 
When the furnace is installed on a platform in a 

crawlspace,  it  must  be  elevated  enough  to  avoid  water 

damage and to allow the evaporator coil to drain.

Return Air -- Horizontal Applications

Return air must be brought in through the end of a fur-

nace installed in a horizontal application. The furnace is 

equipped with a removable bottom panel to facilitate in-

stallation. See figure 11.

 CAUTION

If this unit is being installed in a space serviced by an 

exhaust fan, power exhaust fan, or other device which 

may create a negative pressure in the space, take care 

when sizing the inlet air opening. The inlet air opening 

must be sized to accommodate the maximum volume 

of exhausted air as well as the maximum volume of 

combustion air required for all gas appliances serviced 

by this space.

Summary of Contents for SL280135V60D

Page 1: ...ommunicating applications In non communicating applications the Lennox ComfortSense 7500 thermostat may be used as well as other non communicating thermostats In all cases setup is critical to ensure...

Page 2: ...9 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side...

Page 3: ...STION AIR INDUCER BLOWER ASSEMBLY BURNER BOX INNER BLOWER ACCESS PANEL ACCESS PANEL SIGHT GLASS COMBUSTION AIR INDUCER PRESSURE SWITCH GAS VALVE CONTROL BOX Includes two stage integrated control trans...

Page 4: ...d protective clothing Certifications SL280UHV units are CSA International certified to ANSI Z21 47 In the USA installation of gas furnaces must conform with local building codes In the absence of loca...

Page 5: ...ter during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit SL280UHV units may be used for he...

Page 6: ...information has been reprinted with permission from the National Fuel Gas Code ANSI Z223 1 This reprinted material is not the complete and official position of the ANSI on the referenced subject whic...

Page 7: ...FIGURE 3 Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined air can be brought in by providing two permanent openings between the two spac es Each...

Page 8: ...the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 645 mm2 pe...

Page 9: ...The bolt and washer must be removed before the furnace is placed into opera tion After the bolt and washer have been removed the rigid leg will not touch the blower housing RIGID LEG remove shipping b...

Page 10: ...OW Single Side Return Air with transition and filter FIGURE 9 FIGURE 10 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits ar...

Page 11: ...ce Either suspend the furnace from roof rafters or floor joists as shown in figure 13 or install the furnace on a platform as shown in figure 14 Typical Horizontal Application Unit Suspended in Attic...

Page 12: ...more frequently during the winter and the indoor coil to freeze in the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications...

Page 13: ...it is installed the flue transition must be in the 9 o clock 12 o clock or 3 o clock position If necessary reposition the combustion air inducer pres sure switch and or make up box as needed per the f...

Page 14: ...re switch HORIZONTAL LEFT POSITION Side Vent Discharge Disconnect pressure switch hose from barbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to f...

Page 15: ...The exhaust vent for this furnace must be securely connected to the furnace flue transition at all times FLUE TRANSITION COLLAR VENT CONNECTION VENT PIPE min 6 length DISCONNECTED VENT WARNING STICKE...

Page 16: ...s been sized according to the provided venting tables and the vent pipe manufacturer s instructions A fan assisted furnace may be commonly vented into an existing lined masonry chimney if the followin...

Page 17: ...xceed 7 times the smallest listed appliance categorized vent area drafthood outlet area or flue collar area unless designed according to approved engineering methods 6 The entire length of single wall...

Page 18: ...he provided venting tables If the existing venting system does not meet these requirements it must be resized TABLE 3 Capacity of Type B Double Wall Vents with Type B Double Wall Connectors Serving a...

Page 19: ...51 128 66 195 3 24 47 37 87 53 139 67 210 10 1 22 43 34 78 49 123 65 189 2 23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 1...

Page 20: ...es which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and...

Page 21: ...require the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type IMPORTANT Compounds used on threaded join...

Page 22: ...en testing pressure of gas lines gas valve must be disconnected and isolated See figure 28 Gas valves can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c MANUAL MAIN...

Page 23: ...mage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit rating plate NOTE Unit nameplate states maximum current draw Maximum over current protection allowed is shown in...

Page 24: ...on the C terminal of the icomfort communication terminal strip RSBus Using an additiona wire come off C terminal and wire nut all the extra wires together Termination on the outdoor control must match...

Page 25: ...PTIONAL DISCHARGE AIR SENSOR CLIP ON BOARD LINK W915 Y1 TO Y2 FOR TWO STAGE OPERATION iComfort THERMOSTAT Communicating systems using the iComfort thermostat require four thermostat wires between the...

Page 26: ...wire is 18 RSBus Rf W Gh Gs Cf HVAC EQUIP DEHUMIDIFIER CONTROL HVAC EQUIPMENT DH STANDARD 1 OR 2 STAGE AC OR HP UNIT 24V IN JUMPER iComfort ENABLED FURNACE iComfort ENABLED FURNACE iComfort THERMOSTA...

Page 27: ...N DO NOT CUT ANY ON BOARD LINKS S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2...

Page 28: ...915 2 STAGE COMPR S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat with humidity control OFF CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM OR HARMONY S1 T STAT F...

Page 29: ...T ON BOARD LINK W951 HEAT PUMP T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas he...

Page 30: ...BOARD LINK W914 DEHUM OR HARMONY T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas...

Page 31: ...Page 31 FIGURE 32 SL280UHV Schematic Wiring Diagram...

Page 32: ...HEAT DEMAND FROM 1ST STAGE T STAT R CLASS 2 VOLTAGE TO THERMOSTAT G MANUAL FAN FROM T STAT C THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD TR CHASIS GROUND GRD Y1 THERMOSTAT 1ST STAGE COOL SI...

Page 33: ...lay time that the blower operates after the heating de mand has been satisfied can be adjusted by moving switches 3 and 4 on the integrated control The unit is shipped from the factory with a blower o...

Page 34: ...at 100 until demand is satisfied Once demand is met motor ramps down to stop OFF OFF 100 CFM COMPRESSOR DEMAND Switches 11 12 and 13 Heating Mode Blower Speed The switches are factory set to the OFF...

Page 35: ...board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control W915 must be cut if two stage cooling will be used If the Y1 to Y2 link is not cut the outdoor unit wil...

Page 36: ...Heating Speed cfm Second Stage Heating Speed cfm 24 1300 1420 18 1250 1335 12 1185 1285 6 1145 1240 Factory Default 1070 1170 6 1015 1100 12 970 1035 18 880 980 COOLING 1 Cooling Speed DIP Switch Set...

Page 37: ...DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1420 1565 18 1355 1490 12 1285 1415 6 1215 1335 Factory Default 1145 1260 6 1080 1185 12 1010 1110 18 940 1035 COOL...

Page 38: ...Pressure Range HEATING 1 Heating Speed DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1875 2065 18 1785 1965 12 1695 1865 6 1605 1765 Factory Default 1515 1665 6...

Page 39: ...PRECISION MODE operates independent of a Y1 demand Normal Operation 1 On On On Acceptable 24 VAC High 100 Dehumidification mode begins when humidity is greater than set point Dehumidification Call 2 O...

Page 40: ...oom space to maintain a cooler room thermostat setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE only active on a Y1 thermostat demand Normal Operation 1 On On On On Accepta...

Page 41: ...rners will automatically light The ignitor does not get hot when there is no call for heat on units with an automat ic ignition system WARNING If you do not follow these instructions exactly a fire or...

Page 42: ...al 2 cu ft Dial 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Supply Line Pressure White Rodgers Gas Valve An inlet post located on the gas valve provides a...

Page 43: ...3 034 032 4 9 10 0 4 9 10 0 4 9 10 0 11 0 1 This is the only permissible derate for these units 2 Natural gas high altitude orifice kit required 3 A natural to L P propane gas changeover kit is necess...

Page 44: ...trol The integrated control runs a self diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts The combustion air i...

Page 45: ...nitiates a second stage on delay factory set at 7 minutes adjustable to 12 minutes 5 If the heating demand continues beyond the secondstage on delay the integrated control energizes the combustion air...

Page 46: ...h air grilles and louvers on the unit and in the room where the furnace is installed must be properly sized open and unobstructed to provide combustion air 10 Inspect the furnace venting system to mak...

Page 47: ...he burner manifold assembly to the vestibule panel and remove theassembly from the unit 4 To clean burners run a vacuum cleaner with a soft brush attachment over the face of burners Visually inspect i...

Page 48: ...rts Upper access panel Blower panel Top cap Control Panel Parts Transformer Two stage variable speed integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel Blower housing M...

Page 49: ...ss the flame signal mode The integrated control will display the flame current on 7 segment LED in in micro amps uA Flame signal mode is exited after any of the following Power is reset Pressing and h...

Page 50: ...clears 5 seconds after fault recovered E111 Low line voltage Reverse line power voltage wiring System resumes normal operation 5 seconds after fault recovered E112 Ground not detected System shuts dow...

Page 51: ...riate feature will be set as installed and that could be seen in About screen In normal operation after control recognizes sensors alarm will be sent if valid temperature reading is lost To get rid of...

Page 52: ...ect operation and restriction Resumes normal operation after fault is cleared E227 Low pressure switch open during trial for ignition or run mode Check pressure inches w c of low pressure switch closi...

Page 53: ...ctions 1 hour soft lockout Clears when calibration has finished successfully E290 Ignitor circuit fault Failed ignitor or triggering cir cuitry Measure resistance of hot surface ignitor Replace if ope...

Page 54: ...tween R O on integrated control with non communicating outdoor unit Dual fuel module required for heat pump application Configuration link R to O needs to be restored Replace link or hard wire Applica...

Page 55: ...button next to 7 segment LED display until solid P symbol appears Release button Turn room thermostat to OFF Solid P starts blinking on 7 Segment LED Push and hold button Integrated control will disp...

Page 56: ...OFF NO INDUCER OFF AFTER POST PURGE HARD LOCKOUT ERROR CODE FLASHES YES YES YES 1 2 1 LOW PRESSURE SWITCH OPENS 1 2 HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOCKOUT 3 IN...

Page 57: ...ZED ONLY FOR 1ST REQUEST FOR 2ND STAGE HEAT YES CALL FOR HEAT SATISFIED INDUCER SWITCHED TO HIGH SPEED SINGLE STAGE THERMOSTAT 2 STAGE THERMOSTAT NO INDUCER SWITCHED TO LOW SPEED 5 MINUTE DELAY ERROR...

Page 58: ...2ND STAGE CALL FOR HEAT SATISFIED NO YES DE ENERGIZE 2ND STAGE GAS VALVE INDUCER SPEED SWITCHED TO LOW SPEED 1 2 3 1ST STAGE HEAT 1ST STAGE CALL FOR HEAT SATISFIED NO YES GAS VALVE DE ENERGIZED INDUC...

Page 59: ...RAMPING PROFILES THE SPECIFIC PROFILE IS SELECTED USING THE 1 1 2 2 1 1 1 2 2 DE ENERGIZE 1ST STAGE COOLING CONTACTOR COMPRESSOR FAN 2ND STAGE COOLING REQUEST STILL ACTIVE COOLING REQUEST STILL ACTIV...

Page 60: ...ST FOR HEAT RECEIVED REQUEST FOR COOLING RECEIVED GO TO CALL FOR 1ST STAGE HEAT YES GO TO CALL FOR COOLING 1 1 1 4 YES NO CALL FOR FAN INDOOR BLOWER ON CONTINUOUS FAN SPEED MAINTAIN INDOOR BLOWER AT C...

Reviews: