Operating and Temperature Pressures

Minor variations in these pressures may be expected due to differences in installations. Significant differences could mean
that the system is not properly charged or that a problem exists with some component in the system.

Table 4. Normal Operating Pressures (10 and S5 psig)*

IMPORTANT

Use this table to perform maintenance checks; it is not a procedure for charging the
system. Minor variations in these pressures may be due to differences in installations.
Significant deviations could mean that the system is not properly charged or that a
problem exists with some component in the system.

Model

−024

−030

−036

−042

−048

−060

 

°

F (

°

C)**

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

65 (18.3)

234

139

236

134

226

134

232

137

232

132

236

131

70 (21.1)

249

140

251

135

245

135

249

139

249

133

254

132

75 (23.9)

268

141

271

138

266

137

270

140

268

134

273

133

80 (26.7)

289

142

291

139

287

138

291

141

288

135

294

135

85 (29.4)

310

142

312

140

310

139

314

142

311

136

317

136

90 (32.2)

334

144

335

142

333

140

338

143

333

137

340

137

95 (35.0)

358

145

358

142

358

141

363

144

357

138

364

139

100 (37.8)

383

146

383

143

383

143

389

145

380

139

389

140

105 (40.6)

408

147

409

144

410

144

419

147

406

140

416

142

110 (43.3)

436

148

436

145

437

145

447

148

433

142

444

143

115 (46.1)

465

150

467

147

464

146

480

149

462

143

475

145

*

Typical pressures only, expressed in psig (/− 10 and vapor+/− 5 psig); indoor match up, indoor air quality, and indoor load will cause the pressures
to vary. These operating pressures are also listed on the unit charging sticker (580005−01) located on the access panel.

** Temperature of air entering outdoor coil.

Table 5. HFC−410A Temperature (° Fahrenheit)  Pressure (Psig)

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

32

100.8

48

137.1

63

178.5

79

231.6

94

290.8

110

365.0

125

445.9

141

545.6

33

102.9

49

139.6

64

181.6

80

235.3

95

295.1

111

370.0

126

451.8

142

552.3

34

105.0

50

142.2

65

184.3

81

239.0

96

299.4

112

375.1

127

457.6

143

559.1

35

107.1

51

144.8

66

187.7

82

242.7

97

303.8

113

380.2

128

463.5

144

565.9

36

109.2

52

147.4

67

190.9

83

246.5

98

308.2

114

385.4

129

469.5

145

572.8

37

111.4

53

150.1

68

194.1

84

250.3

99

312.7

115

390.7

130

475.6

146

579.8

38

113.6

54

152.8

69

197.3

85

254.1

100

317.2

116

396.0

131

481.6

147

586.8

39

115.8

55

155.5

70

200.6

86

258.0

101

321.8

117

401.3

132

487.8

148

593.8

40

118.0

56

158.2

71

203.9

87

262.0

102

326.4

118

406.7

133

494.0

149

601.0

41

120.3

57

161.0

72

207.2

88

266.0

103

331.0

119

412.2

134

500.2

150

608.1

42

122.6

58

163.9

73

210.6

89

270.0

104

335.7

120

417.7

135

506.5

151

615.4

43

125.0

59

166.7

74

214.0

90

274.1

105

340.5

121

423.2

136

512.9

152

622.7

44

127.3

60

169.6

75

217.4

91

278.2

106

345.3

122

428.8

137

519.3

153

630.1

45

129.7

61

172.6

76

220.9

92

282.3

107

350.1

123

434.5

138

525.8

154

637.5

46

132.2

62

175.4

77

224.4

93

286.5

108

355.0

124

440.2

139

532.4

155

645.0

47

134.6

78

228.0

109

360.0

140

539.0

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for Signature XC17

Page 1: ...lled prior to operating the system INSTALLATION INSTRUCTIONS Dave Lennox Signature Collection XC17 Units AIR CONDITIONER 506510 01 04 10 Supersedes 506498 01 RETAIN THESE INSTRUCTIONS FOR FUTURE REFER...

Page 2: ...SCHARGE AIR 024 41 1040 030 THROUGH 060 47 1194 16 7 8 429 8 3 4 222 26 7 8 683 3 3 4 95 30 3 4 781 3 1 8 79 UNIT SUPPORT FEET Model Number Identification C 17 036 Unit Type C Air Conditioner Series N...

Page 3: ...HARGE LINE TEMPERATURE SENSOR LOW PRESSURE SWITCH HIGH PRESSURE SWITCH THERMOSTAT COMPRESSOR HARNESS SR1 SOUND DOME VIBRATION ISOLATOR SLEEVE LOCATIONS DO NOT REMOVE GROUND LUG HIGH VOLTAGE FIELD CONN...

Page 4: ...um Fully insert the wrench into the valve stem recess Service valve stems are factory torqued from 9 ft lbs for small valves to 25 ft lbs for large valves to prevent refrigerant loss during shipping a...

Page 5: ...ng is completed replace service port cap and tighten as fol lows 1 2 3 4 5 6 7 8 9 10 11 12 1 6 TURN Operating Angle Type Service Valve 1 Remove stem cap with an appropriately sized wrench 2 Use a ser...

Page 6: ...ng when the pressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low...

Page 7: ...stallation clearance requirements POSITIONING CONSIDERATIONS Consider the following when positioning the unit S Some localities are adopting sound ordinances based on the unit s sound level registered...

Page 8: ...unstable an uneven surface With unit positioned at installation site perform the following 1 Remove two side louvered panels to expose the unit base 2 Install the brackets as illustrated in Figure 4...

Page 9: ...E DRILL 1 8 TWO 90 ELBOWS INSTALLED IN LINE SET WILL REDUCE LINE SET VIBRATION INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FRO...

Page 10: ...s illustrated in Detail D with the screw side as close to the unit as possible Then in a continuous motion 1 Slightly rotate and guide the lip of top tab inward as illustrated in Detail A and C then u...

Page 11: ...50 5 15 042 3 8 10 7 8 22 3 8 10 7 8 22 048 060 3 8 10 1 1 8 29 3 8 10 1 1 8 29 Field Fabricated NOTE Some applications may required a field provided 7 8 to 1 1 8 adapter NOTE When installing refriger...

Page 12: ...t is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WOOD BLOCK BETWEEN S...

Page 13: ...tion on the vapor service valve NOTE The fixed orifice or check expansion valve metering device at the indoor unit will allow low pressure nitrogen to flow through the system NITROGEN HIGH LOW USE REG...

Page 14: ...y reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR unit GAUGE MANIFOLD INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 22 TO BE USED FOR FLUSHING LIQUI...

Page 15: ...econnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector...

Page 16: ...ester POE oils are used in Lennox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce...

Page 17: ...valve to the center port of the manifold gauge set D Adjust dry nitrogen pressure to 150 psig 1034 kPa Open the valve on the high side of the manifold gauge set in order to pressurize the line set an...

Page 18: ...29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the ma...

Page 19: ...AKER PANEL Refer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved f...

Page 20: ...ee Figures 10 and 10 for typical configurations 3 A Run 24VAC control wires through hole with grommet B Make 24VAC control wire connections to Main Control Any excess high voltage field wiring should...

Page 21: ...Page 21 XC17 SERIES Figure 7 Typical XC17 Wiring Downloaded from ManualsNet com search engine...

Page 22: ...INFORMATION CONCERNING JUMPERS LOOP AND CONNECTIONS FOR THE MAIN CONTROL DS13 and DS15 DS11 and DS14 LED ALERT CODES LED ALERT CODES CUT FOR HUMIDITROL ENHANCED DEHUMIDIFICATION ACCESSORY EDA APPLICA...

Page 23: ...M fan motor 24VDC output connection 2 E28 FAN C ECM common connection for ECM fan E30 Six position square pin header E30 provides connections for the temperature sensors DIS YELLOW Pins 5 and 6 DIS 5...

Page 24: ...rol comes from factory with metal jumpers across W1 W2 and W3 For one stage electric heat do not remove metal jumpers Outdoor sensor for outdoor temperature display Optional 1 2 3 5 1 2 5 On board lin...

Page 25: ...using the ComfortSense 7000 Y0349 with Control LSOM feature Resistor kit not required when using ComfortSense 7000 Y2081 Outdoor sensor for outdoor temperature display Optional Cut on board link W914...

Page 26: ...h The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 6 S...

Page 27: ...entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb Wet bulb F A 72 B 64 C 53 air flow air flow All temperatures are expressed in F 1 Determine the desired DT Measure e...

Page 28: ...e set 3 8 9 5 mm 3 ounce per 5 85 g per 1 5 m If line length is greater than 15 ft 4 6 m add this amount If line length is less than 15 ft 4 6 m subtract this amount Refrigerant Charge per Line Set Le...

Page 29: ...if less than shown add refrigerant 1 Confirm proper airflow across coil using Figure 12 2 Compare unit pressures with Table 4 Normal Operating Pressures 3 Use SUBCOOLING to correctly charge unit or to...

Page 30: ...s only expressed in psig liquid 10 and vapor 5 psig indoor match up indoor air quality and indoor load will cause the pressures to vary These operating pressures are also listed on the unit charging s...

Page 31: ...r short the control will de energize all the outputs and anti short cycle timer is started Discharge sensor faulty alert LED code will be displayed OUTDOOR AMBIENT TEMPERATURE RT13 If the outdoor ambi...

Page 32: ...VAC power to the outdoor unit s Main Control 2 If the jumper remains on the TEST pins for longer than five seconds the Main Control will ignore the JUMPER ON TEST pins and revert to normal operation Y...

Page 33: ...42 3 24525 9 9 62712 27 0 210805 90 6 7225 41 7 24934 9 3 63752 27 8 217080 89 4 7444 41 1 25349 8 8 64812 28 7 223677 88 1 7666 40 5 25769 8 3 65895 29 5 230621 86 9 7890 39 9 26195 7 7 67000 30 4 2...

Page 34: ...5 75 0 10495 232 4 492 163 2 1590 119 3 3816 74 1 10749 230 5 507 162 3 1617 118 5 3877 73 1 11014 228 6 523 161 4 1644 117 8 3940 72 1 11289 226 7 538 160 5 1672 117 0 4005 71 1 11575 224 9 553 159 7...

Page 35: ...r power up existing code will display for 60 seconds and then clear 2 Automatic Reset After an alert is detected the Main Control continues to monitor the unit s system and compressor operations When...

Page 36: ...system operating pressures and compare to unit charging charts 4 Make sure all pressure switches and sensors have secure connec tions to system to prevent refrigerant leaks or errors in pressure and...

Page 37: ...coil is dirty 6 Liquid line restriction filter drier blocked if present 7 Thermostat is malfunctioning S Check thermostat sub base or wiring for short cir cuit S Check thermostat installation locatio...

Page 38: ...ailed 2 Open circuit in compressor start wiring or connec tions S Check wiring and connectors between supply and the compressor S terminal 3 Compressor start winding is damaged S Check compressor moto...

Page 39: ...Page 39 XC17 SERIES Figure 19 High Pressure Switch Operation Downloaded from ManualsNet com search engine...

Page 40: ...Page 40 506510 01 Figure 20 Low Pressure Switch Operation Downloaded from ManualsNet com search engine...

Page 41: ...Page 41 XC17 SERIES Figure 21 High Discharge Temperature Sensor Operation Downloaded from ManualsNet com search engine...

Page 42: ...for a single stage outdoor unit see table 11 VERIFYING CORRECT DC OUTPUT VOLTAGE J2 The following three methods can be used to determine whether the fan motor is operating at the correct RPMs based o...

Page 43: ...ge Operation Low Stage ECM1 Y1 ONLY One slow flash then short pause RPM Indicator NOTE There is a long pause between stage operationand RPM indicator See Tables 1 and 2 for LED RPM indicator RPM Indic...

Page 44: ...M TERMINALS SEE TABLE 11 FOR OPTIMAL DC VOLTAGE BASED ON CFM PROFILE USED COM FAN PWM OUT GREEN RED BROWN RED BLACK YELLOW YELLOW RED RED BLACK GREEN YELLOW BLACK PWM FAN CONTROL YELLOW BLACK YELLOW B...

Page 45: ...W WIRE GREEN RED BROWN RED BLACK YELLOW YELLOW RED RED BLACK GREEN YELLOW BLACK PWM FAN CONTROL YELLOW BLACK YELLOW BLUE SEE TABLE 11 FOR CFM PROFILE SELECTION OPTIONS TO MAIN CONTROL EXT PWR R BLACK...

Page 46: ...hat the motor does operate J2 1 Verify main 240 volt power if OFF to unit 2 Remove both wires brown and black from the J2 terminal on the fan motor control 3 Room thermostat should be in OFF position...

Page 47: ...ock airflow across the coil e g pet urine cottonwood seeds fertilizers fluids that may contain high levels of corrosive chemicals such as salts Sea Coast Moist air in ocean locations can carry salt wh...

Page 48: ...5 Indoor Unit The indoor unit s evaporator coil is equipped with a drain pan to collect condensate formed as your system removes humidity from the inside air Have your dealer show you the location of...

Page 49: ...on unit or installation instructions for required subcooling and approach temperatures Subcooling A B SUBCOOLING Saturated Condensing Temperature A minus Liquid Line Temperature B Approach A B APPROA...

Reviews: