TYPICAL ELECTROMECHANICAL THERMOSTAT

FIGURE 1

Placing Unit Into Operation

 

WARNING

Danger of explosion and fire. Can cause
injury or product or property damage.
You must follow these instructions ex-
actly.

Gas Valve Operation for Honeywell
VR8205Q/VR8305Q (figure 2)

HONEYWELL VR8205Q/VR8305Q SERIES GAS VALVE

Gas valve knob is shown in 

OFF

 position.

FIGURE 2

LOW FIRE

ADJUSTMENT

HIGH FIRE

ADJUSTMENT

INLET

PRESSURE

TAP

MANIFOLD

PRESSURE

TAP

1− Set thermostat to lowest setting.

2− Turn off all electrical power to furnace.

3− This furnace is equipped with an ignition device which

automatically lights the burner. Do 

not

 try to light the

burner by hand.

4− Open or remove the heat section access panel.

5− Turn the knob on the gas valve clockwise 

 to

OFF"

. Do not force.

6− Wait five (5) minutes to clear out any gas. If you then

smell gas, 

STOP!

 Immediately call your

gas supplier from a neighbor’s phone. Follow the gas

supplier’s instructions. If you do not smell gas, go to

the next step.

7− Turn the knob on the gas valve counterclockwise 

to 

ON"

. Do not force.

8− Close or replace the heat section access panel.

9− Turn on all electrical power to furnace.

10− Set thermostat to desired setting.

11− The ignition sequence will start.

12− If the furnace does not light the first time (gas line not

fully purged), it will attempt up to two more ignitions

before locking out.

13− If lockout occurs, repeat steps 1 through 10.

14− If the furnace will not operate, follow the instructions

Turning Off Gas to Furnace" and call your service

technician or gas supplier.

Turning Off Gas to Furnace

1− If using an electromechanical thermostat, set to the

lowest setting.

2− Before performing any service, turn off all electrical

power to the furnace.

3− Open or remove the heat section access panel.

4− Turn the knob on the gas valve clockwise 

 to

OFF"

. Do not force.

5− Close or replace the heat section access panel.

 

WARNING

Danger of explosion. Can cause injury or
death. Do not attempt to light manually.
Unit has a direct spark ignition system.

Summary of Contents for SGA420

Page 1: ...on and service must be per formed by a qualified installer ser vice agency or the gas supplier D Do not try to light any appliance D Do not touch any electrical switch do not use any phone in your bui...

Page 2: ...COILS OPTIONAL BURNERS GAS VALVES 2 CONDENSER COILS 4 CONTROL BOX COMPRESSORS 4 CONDENSER FANS 6 BLOWERS FILTERS ELEVEN 16 x 25 x 2 406 x 635 x 51mm OR 16 X 25 X 4 406 X 635 X 102mm ECONOMIZER OPTION...

Page 3: ...errors can cause improper and dangerous operation Verify proper operation after servicing WARNING Danger of electrical shock explosion and fire Improper servicing could result in dangerous operation...

Page 4: ...llow the gas supplier s instructions If you do not smell gas go to the next step 7 Turn the knob on the gas valve counterclockwise to ON Do not force 8 Close or replace the heat section access panel 9...

Page 5: ...Service To maintain efficiency and longevity your equipment must be serviced yearly by a qualified service technician Failure to provide proof of service can void warranty CAUTION Label all wires prio...

Page 6: ...t the position of the flame sensor Sensor should be centered in the path of the flame 3 Before each heating season examine the burners for any deposits or blockage which may have occurred Clean burner...

Page 7: ...e box cover Clean the flue box with a wire brush as required 3 Clean the tubes with a wire brush 4 Reassemble the unit The flue box cover gasket and combustion air inducer gasket should also be replac...

Page 8: ...8 The unit will operate at maximum heating input 3 Measure the manifold pressure at the gas valves Manifold pressures should be GV1 GV3 Natural 4 0 w c LP 10 8 w c GV4 GV5 Natural 3 7 w c LP 10 5 w c...

Reviews: