Lennox SCU14M Series Installation And Maintenance Instructions Manual Download Page 7

# 504,465M

Page 7

and two sets of gauges (one for use with R22 and one for
use with R410A).

Flushing Procedure

IMPORTANT:

 The line set and/or indoor coil must be

flushed with at least the same amount of refrigerant that
previously charged the system. Check the charge in the
flushing cylinder before flushing the unit.

1. Remove existing R22 refrigerant using the appropriate

procedure.

If the existing outdoor unit is not equipped with shutoff
valves, or if the unit is not operational AND you plan to
use the 

existing

 R22 refrigerant to flush the system:

Disconnect all power to the existing outdoor unit.
Connect the existing unit, a clean recovery cylinder,
and the recovery machine according to the instruc-
tions provided with the recovery machine. Remove all
R22 refrigerant from the existing system. Refer to the
gauges after shutdown to confirm that the entire
system is completely void of refrigerant. Disconnect
the liquid and suction lines from the existing outdoor
unit.

If the existing outdoor unit is equipped with manual
shutoff valves AND you plan to use 

new

 R22 refriger-

ant to flush the system:

Start the existing R22 refrigerant system in cooling
mode and close the liquid line valve. Pump all the
existing R22 refrigerant back into the outdoor unit.
(It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.)
When the low side system pressures reach 0 psig,
close the suction line valve. Disconnect all power to
the existing outdoor unit. Refer to the gauges after
shutdown to confirm that the valves are not allowing
refrigerant to flow back into the low side of the sys-
tem. Disconnect the liquid and vapor lines from the
existing outdoor unit.

2. Remove the existing outdoor unit. Set the new R410A

unit and follow the brazing connection procedure (see
page 5) to make line set connections. 

Do not install

provided R410A check/expansion valve at this
time.

Make low voltage and line voltage connections to the
new outdoor unit. 

Do not turn on power to the unit

or open the outdoor unit service valves at this
time.

3. Remove the existing refrigerant flow control orifice or

thermal expansion valve before continuing with
flushing procedures. The existing devices are not
approved for use with R410A refrigerant and may

prevent proper flushing. Use a field-provided fitting to
reconnect the lines.

4. Remove the pressure tap valve cores from the

SCU14M unit’s service valves. Connect an R22
cylinder with clean refrigerant to the suction service
valve. Connect the R22 gauge set to the liquid line
valve and connect a recovery machine with an empty
recovery tank to the gauge set.

5. Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the
existing system line set and indoor coil.

6. Invert the cylinder of clean R22 and open its valve to

allow liquid refrigerant to flow into the system through
the suction line valve. Allow the refrigerant to pass
from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.

7. After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the R22 vapor is recovered. Allow the recovery
to pull a vacuum on the system.

NOTE:

 A single system flush should remove all of the

mineral oil from the existing refrigerant lines and
indoor coil. A second flushing may be done (using
clean refrigerant) if insufficient  amounts of mineral oil
were removed during the first flush. 

Each time the

system is flushed, you must allow the recovery
machine to pull a vacuum on the system at the
end of the procedure.

8. Close the valve on the inverted R22 cylinder and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

9. Use nitrogen to break the vacuum on the refrigerant

lines and indoor coil before removing the recovery
machine, gauges, and R22 refrigerant drum. Re-
install pressure tap valve cores into the SCU14M
service valves.

10. Install the provided expansion valve (approved for use

with R410A refrigerant) in the liquid line at the indoor
coil.

Manifold Gauge Set

Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures. The gauges should be rated
for use with pressures 0 – 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psi of pressure with a 4000 psi burst rating.

Summary of Contents for SCU14M Series

Page 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Page 2: ...m m 9 5 7 6 1 8 5 6 8 5 0 3 6 7 6 3 7 4 8 4 0 M 4 1 U C S n i 8 7 3 3 8 1 2 3 6 1 1 4 3 3 1 8 5 6 2 8 5 8 1 m m 1 6 8 6 1 8 5 6 8 0 3 3 6 7 6 3 7 4 0 6 0 M 4 1 U C S n i 8 7 9 3 8 1 2 3 6 1 1 4 3 9 1...

Page 3: ...ation SCU14M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU14M units are designed for use in expansion v...

Page 4: ...to drafts direct sunshine or other heat sources 3 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit see Figure 2 on this page and Figure 7 on page 14 4 Ground u...

Page 5: ...e of nicks or dents and must be deburred I D and O D 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduction of m...

Page 6: ...Tighten to 20 30 ft lbs Use backup wrench on all wrench flats Overtightening will crush the teflon seal and may cause a leak 4 Connect the external equalizer line to the equalizer port on the suction...

Page 7: ...ng procedures The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 4 Remove the pressure tap valve c...

Page 8: ...terclockwise until the valve stem just touches the retaining ring 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove...

Page 9: ...oints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation and Dehydration Evacuating the system o...

Page 10: ...rant charge contained in condensing unit into system Replace and tighten caps Use a back up wrench on the suction and liquid valves when removing or replacing valve caps 4 To open suction valve remove...

Page 11: ...2 4 0 M 4 1 U C S L 1 4 2 2 8 2 6 2 3 3 7 3 4 2 4 S 1 3 1 3 3 1 5 3 1 7 3 1 9 3 1 8 4 0 M 4 1 U C S L 6 2 2 6 6 2 0 1 3 6 5 3 7 0 4 S 0 3 1 2 3 1 5 3 1 7 3 1 9 3 1 0 6 0 M 4 1 U C S L 0 4 2 9 7 2 1 2...

Page 12: ...each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose 2 Condenser fan motor is pre lubricated and sealed No further lubri...

Page 13: ...rmine the correct blower CFM Refer to the unit information service manual for pressure drop tables and proce dure 3 On belt drive blowers check belt for wear and proper tension 4 Check all wiring for...

Page 14: ...APACITOR DUAL C12 B4 B4 BLACK RUN ORANGE COMMON K1 S87 S1 ROOM THERMOSTAT TO INDOOR UNIT COMMON 24VAC FAN HEAT W G R Y B1 2 2 2 S4 S1 ROOM THERMOSTAT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH COMPRESSO...

Page 15: ...n belts fuses or other consumable items 3 Damage caused by misuse failure to maintain properly accidents or acts of God 4 External wiring piping venting or attachment of accessory products not integra...

Reviews: