Chart 12
Chart 13
Chart 14
Use frozen oil
Bend the pipe with thumb
Min-radius 100mm
Make the ends
straight
2. Locate The Pipe
1) Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then
set on the fittings such as the wall conduit and its cover.
2) Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air
in, which will cause water leakage by condensation.
3) Pass the bound connecting pipe through the wall conduit from outside. Be careful of the
pipe allocation to do no damage to the tubing.
3. Connect the pipes.
4. Then, open the stem of stop valves of the outdoor unit to make the refrigerant pipe conne-
cting the indoor unit with the outdoor unit fluently flow.
5. Be sure of no leakage by checking it with leak detector or soap water.
6. Cover the joint of the connecting pipe to the indoor unit with the soundproof/insulating
sheath (fittings), and bind it well with the tapes to prevent leakage.
A
90+4
_
45+2
_
A
(
mm
)
f
6. 5mm
3
f
9.53mm
f
12.7mm
f
16mm
f
19mm
8.7
8.3
15.8
15.4
12.4
12.0
19.0
18.6
23.3
22.9
1. Cut a pipe with a pipe cutter.
2. Insert a flare nut into a pipe and flare the pipe.
REFRIGERANT PIPE CONNECTION
Outside-
diameter
Max
Min
90
lean
crude burr
Chart 16
Chart 15
Table 1
Too large torque will harm the bellmouthing and
too small will cause leakage.
Please determine
the torque according to Table 2.
Chart a
Table 2
Put the
connecting tubing at the proper position,
wrench
the
nuts
with
hands
then
fasten
it
with
a wrench. (Refer to Chart a)
Caution
f
9.53
26~30
.
N m
f
12.7
26~30
.
N m
Fasten the nut
Tubing Size
Torque
f
19
9
35~40
.
N m
Be
sure
to
use the same insulating materials when you buy the brass pipe. (More than
9mm thick)
Use the market brass pipe.
8