background image

Page 20

Troubleshooting:  Burner starts, but no flame is established.

Source

Procedure

Causes

Correction

Check tank gauge or use dip
stick.

No oil in tank

Fill tank.

Oil Supply

Coat dip stick with litmus paste
and insert into bottom of tank.

Water in oil tank

If water depth exceeds 1 inch,
pump or drain water.

Listen for pump whine.

Tank shut−off valve closed

Open valve.

Oil line filter is plugged

Replace filter cartridges.

Listen for pump whine.

Kinks or restriction in oil line

Repair or replace oil line.

Oil Filters & Oil Line

Plugged fuel pump strainer

Clean strainer or replace pump.

O

te s & O

e

Open bleed valve or gauge port.
Start the burner No oil or milky

Air leak in oil supply line

Locate and correct leak.

Start the burner. No oil or milky
oil indicates loss or prime.

Air leak in oil supply line

Tighten all connections.

Oil P

Install pressure gauge on pump

d

d

Sh

ld

t

Pump is partially or completely
frozen. No pressure and the
motor locks out on overload.

Replace pump.

Oil Pump

p

g

g

p

p

and read pressure. Should not
be less than 140 psi.

Coupling disengaged or broken
− no pressure

Re−engage or replace coupling.

Fuel pressure too low

Adjust to 100 psi.

Disconnect ignition leads. Ob-
serve the oil spray (gun assem-

Nozzle orifice plugged

Replace nozzle with the same

Nozzle

serve the oil spray (gun assem
bly must be removed from unit).
Inspect the nozzle for plugged

Nozzle strainer plugged

Replace nozzle with the same
size, spray angle, and spray
type

spect t e o

e o p ugged

orifice or carbon build−up around
orifice.

Poor or off center spray

type.

Fouled or shorted electrodes

Clean electrode leads

Dirty electrodes and leads

Clean electrode leads.

Eroded electrode tips

Cl

l

t d ti

d

t

Improper electrode gap spacing

Clean electrode tips and reset
the gap to 5/32 inches and cor-

Ignition Electrodes

Remove gun assembly and in-
spect electrodes and leads.

Improper position of electrode
tips

the gap to 5/32 inches and cor-
rectly position tips.

Bad buss bar connection

Retension and realign.

Cracked or chipped insulators

Replace electrode.

Cracked or burned lead insula-
tors

Replace electrode leads.

I

iti

Connect ignition leads to the
t

f

St t b

d b

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or call the power company.

Ignition

Transformer

g

transformer. Start burner and ob-
serve spark. Check line voltage
to transformer primary.

Burned out transformer wind-
ings.

Replace the transformer.

to transformer primary.

No spark or weak spark

Properly ground the transformer
case.

B

M t

Motor does not come up to
speed and trips out on overload.
T

ff

d

t t bl

Low line voltage

Check voltage at power source.
Correct cause of voltage drop
or the call power company.

 Burner Motor

p

p

Turn off power and rotate blower
wheel by hand to check for bind-
ing or excessive drag

Pump or blower overloading
motor

Correct cause of overloading.

ing or excessive drag.

Faulty motor

Replace motor.

Summary of Contents for OF23Q3/4-105

Page 1: ...OF23 Oil AFII Burner Parts Arrangement 4 Requirements 4 Locate Level Unit 4 Unit Adjustments 5 Venting 6 Flue Connect ions 11 Supply Return Air Plenums 11 Oil Supply Lines Sizing 11 Connect Oil Supply...

Page 2: ...1 2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 OF23Q5 140 154 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406 OF23Q5 140 154R 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 2...

Page 3: ...EAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4 BOX IGNITOR...

Page 4: ...re inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner IMPORTANT An opening to the outside for combustion...

Page 5: ...ct adjustment procedures Nozzle Adjustment Proper adjustment of the nozzle assembly is critical because alignment may have changed during shipping Before the fur nace and oil lines are installed the n...

Page 6: ...ed accord ing to the requirements of the National Fire Protection Asso ciation The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector Make sure t...

Page 7: ...pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system 14 All unused chimney openings should be closed 15 All vent pipe run through unconditioned...

Page 8: ...Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet 1 4 cubic meters per 1 000 Btu 293 W per hour of the combined input rating of...

Page 9: ...Vent Figure 11 NOTE Each air duct opening shall have a free area of at least one square inch 6 4 square centimeters per 2 000 Btu 586 W per hour of the total input rating of all equipment in the enclo...

Page 10: ...common venting system Turn on any exhaust fans such as range hoods and bathroom ex hausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace damp ers 4 Followin...

Page 11: ...pace to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed with the draft control Alternate Side Flue Connections The vent pi...

Page 12: ...or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT...

Page 13: ...asy maintenance Table 4 lists the filters for the OF23 furnace Consult the burner manufacturer s instructions that are in cluded with the unit for further details concerning oil supply pipe connection...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip Figure 17 Typical OF23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical OF23 Wiring Diagram...

Page 16: ...eat exchanger to prevent it from picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the re...

Page 17: ...should still be 0 02 less than the draft pres sure reading taken at the breach You may need to increase the stack draft by adjusting the barometric draft control 7 Stack Temperature Take a stack tempe...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...y control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor Re...

Page 20: ...le for plugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type spect t e o e o p ugged orifice or carbon build up around orifice Poor or off center spray type Foul...

Page 21: ...inues to run d t l k Too much air lean short fire Reduce combustion air check combustion Poor Fire does not lock out of safety fault may be Too little air long dirty fire Increase combustion air check...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: