Troubleshooting:  Burner starts and fires, but lock out on safety.

Source

Procedure

Causes

Correction

Unbalanced fire

Replace nozzle

If burner con-
ti

t

Too much air − −lean short fire

Reduce combustion air − check
combustion.

Poor Fire

tinues to run,
this may be
due to poor

Too little air − − long dirty fire

Increase combustion air − check
combustion.

due to poor
fire. Inspect
fire.

Excessive draft

Adjust barometric damper for
correct draft.

After burner
fires, immedi-
ately jumper

Too little draft or restriction

Correct draft or remove restric-
tion.

ately jumper
across flame
d t

t

t

i

If fire is good,

Dirty cad cell face

Clean cad cell face.

Flame Detector

detector termi-
nals at the pri-
mary control.

If fire is good,
fault is in the
flame detector.
Ch

k d t

Faulty cad cell − exceeds 15000
hms

Replace cad cell.

mary control.

Check detec-
tor circuit.

Loose or defective cad cell
wires

Secure connections or replace
cad cell holder and wire leads.

Primary Control

If burner locks
out on safety,
fault is in the
primary con-
trol.

Primary control circuit defective

Replace primary control.

Troubleshooting:  Burner Starts and Fires, but Loses Flame and Lock Out on Safety

Source

Procedure

Causes

Correction

Unbalanced fire

Replace nozzle

Too much air − − lean short fire

Reduce combustion air − check
combustion.

Too little air − − long dirty fire

Increase combustion air − check
combustion.

Poor Fire

If burner con-
tinues to run
(does not lock

Excessive draft

Adjust barometric damper for
correct draft.

(does not lock
out of safety),
fault may be

Too little draft or restriction

Correct draft or remove restric-
tion.

After burner
fires immedi

If fire is good,

Dirty CAD cell face

Clean CAD cell face.

Flame Detector

fires, immedi-
ately jumper
across flame

If fire is good,
fault is in the
flame detector.
Ch

k d t

Faulty CAD cell − − exceeds
15000 hms

Replace CAD cell.

Flame Detector

across flame
detector termi-
nals at the pri-
mary control

Check detec-
tor circuit.

Loose or defective cad cell
wires

Secure connections or replace
cad cell holder and wire leads.

mary control.

Pump loses prime − air slug

Prime pump at bleed port

If burner loses
flame (does
not lock out on

Pump loses prime − air leak in
supply line

Check supply line for loose con-
nections and tighten fittings.

not lock out on
safety), fault is
in the fuel sys-

Water slug in line

Check oil tank for water (over 1
inch) pump or drain out water.

Oil Supply

in the fuel sys
tem.

Partially plugged nozzle or
nozzle strainer

Replace nozzle.

Restriction in oil line

Clear restriction.

Listen for pump whine

Plugged fuel pump strainer

Clean strainer or replace pump.

Cold oil − outdoor tank

Change to number 1 oil.

Summary of Contents for O23

Page 1: ...the Unit 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 15 Service 1...

Page 2: ...120 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 O23Q5 140 154 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connectio...

Page 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Page 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Page 5: ...llowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTIO...

Page 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Page 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Page 8: ...alled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and whi...

Page 9: ...square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equip ment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Page 10: ...operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common ventin...

Page 11: ...raft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed...

Page 12: ...ar walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Both o...

Page 13: ...mm Oil Filters Cat Number 10 micron filter no mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge...

Page 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip fan off delay switches Figure 17 Typical O23 Wiring Diagram...

Page 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Page 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Page 17: ...rol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency c...

Page 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Page 19: ...ry control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor R...

Page 20: ...ugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type Inspect the nozzle for plugged orifice or carbon build up around orifice Poor or off center spray type Fouled...

Page 21: ...lace nozzle Too much air lean short fire Reduce combustion air check combustion Too little air long dirty fire Increase combustion air check combustion Poor Fire If burner con tinues to run does not l...

Page 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Page 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Reviews: