background image

9

Grille

Side Panel

Figure 9.  Remove Side Panel and Grille

2.  Install suspension rods in the structural 

ceiling or concrete slab in a suitable location. 

 

If the structural ceiling is constructed of concrete, 

install anchors to accept four suitably sized threaded 

rods to suspend the indoor unit. If the structural ceiling 

includes wooden joists, use angle iron or Unistrut 

channel fixed securely in place to accept the threaded 

rods.  

3.  Slide one nut and one washer onto each threaded rod.

Threaded

Rod

Anchor

Wooden

Joist

Threaded

Rod

Angle Iron Bolted

in Place Across 

Wooden Joists

CONCRETE CEILING

USING ANCHORS

ANGLE IRON 

ACROSS WOODEN

JOISTS

Figure 10. Locate Threaded Rods

4.  Use electrical tape to keep the washer from falling off. 

Position the nuts 

5.  Slide a second washer and then a second nut onto 

each rod slightly above the final resting place of the 

hanging brackets. 

6. 

If necessary, install a field-provided isolation grommet 

to prevent transmission of vibration from unit to 

structural ceiling.

 

Threaded Rod

Suspension

Bracket

Leveling

Nut

Washer

Field-Provided

Isolation

Grommet

Figure 11. Locate Bracket on Threaded Rod

7.  Use either a mechanical lifting device or a minimum of 

two people to raise the unit.

8.  Hang the unit by sliding the factory-installed hanging 

brackets on to the threaded rods between the sets of 

washers and nuts. 

9.  Use the leveling nut (beneath hanging brackets) 

to adjust the unit to the correct height. Remove the 

electrical tape holding the upper washers and nuts 

in place and tighten each of the four nuts above the 

brackets down onto the brackets. This will ensure that 

the unit remains level. 

Indoor Unit Condensate Piping Connections

IMPORTANT

Make sure that drain piping is properly routed and 

insulated to prevent both leaks and condensation.

1. 

Use a field-provided hose clamp to secure the drain 

line stub on the side of the cassette base to a field-

supplied 1” (25 mm) drain line.

NOTE: 

Take care not to over-tighten the hose clamp as 

this may damage the drain line stub.

NOTE: 

Connection between stub and drain line must be 

watertight. Apply non hardening plumbing joint 

compound  if needed to ensure a watertight seal. 

2. 

Confirm proper slope (not less than 1/4 inch per foot 

(18 mm per m)) and routing of condensate lines to 

ensure moisture is drained away from the indoor unit.

3.  Drain should be as short as possible and should 

not have any droops or kinks that would restrict 

condensate flow and shall be approved resistant pipe. 

 

There must be a 2-inch (51 mm)  space between  

the  end  of  the  condensate  drain  and  the  final 

termination point (ground, open drain, etc.) to 

ensure that the line will drain freely.

4.  After the system installation is complete, the 

condensate drain line must be checked for leaks and 

proper drainage. If a field-provided condensate pump 

has been installed, it must be checked to ensure proper 

operation. This check is part of the start-up process 

which must be done by the installing contractor.

IMPORTANT

Drain should have a slope of at least ¼ inch per foot and 

should be approved corrosion-resistant pipe. You must 

confirm operation of every drain and pump in the system 

as part of the commissioning procedure.

DRAIN LINE

           Slope at least 1/4”

per foot (18 mm per M)

3 ft. (1 m)

SUPPORT

STRAPS

Figure 12. Indoor Unit Suspended from Ceiling 

using a Properly Sloped Gravity Drain

Summary of Contents for MCFA024S4-*P

Page 1: ...g jurisdiction should be consulted before installation The MCFA and MCFB Ceiling Floor indoor units are matched with an outdoor heat pump unit to create a mini split system that uses HFC 410A refriger...

Page 2: ...door unit will include the following items 1 Assembled Outdoor Unit and the following items Parts Figure Quantity Parts Figure Quantity Drain connector 1 Seal ring 1 Indoor Outdoor Unit Match Ups Outd...

Page 3: ...1 phase 60hz Nominal Cooling Capacity 018 1 5 tons 024 2 tons 036 3 tons 048 4 tons Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M CF A 018 S 4 1 P Unit Type CF...

Page 4: ...frigerant lines individually to prevent sweating UV rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable fiel...

Page 5: ...es 40 1 4 25 53 3 4 15 3 8 16 mm 1023 635 1365 391 406 MPB018S4S P inches 36 21 1 4 27 5 8 14 1 4 13 3 4 mm 914 540 702 363 350 MPB024S4S P MPB036S4S P inches 40 1 2 26 1 2 31 7 8 16 1 8 15 7 8 mm 103...

Page 6: ...P 50 5 8 1286 47 3 8 1203 MCFA048S4S P 65 1651 61 3 4 1568 MCFB018S4S P 42 1 8 1070 39 991 Figure 3 MCFA and MCFB Indoor Unit Dimensions Inches mm System Clearances Outdoor Unit 24 610 Air Outlet Air...

Page 7: ...ervice valve stems are factory torqued from 9 ft lbs 12 N for small valves to 25 ft lbs 34 N for large valves to prevent refrigerant loss during shipping and handling Using an Allen wrench rated at le...

Page 8: ...on page 7 for minimum clearances Place the MCFA or MCFB on a wall which is both ca pable of supporting the unit s weight and which is con structed to enable the unit to fit flush on the wall An uneven...

Page 9: ...own onto the brackets This will ensure that the unit remains level Indoor Unit Condensate Piping Connections IMPORTANT Make sure that drain piping is properly routed and insulated to prevent both leak...

Page 10: ...intercom Electrical interference and radio frequencies from any of these sources may affect operation Since water drains from the outdoor unit during vari ous stages of operation do not place anything...

Page 11: ...amples are When prevailing winds are from the air inlet side then position the wind barrier a minimum of 12 inches 305 mm from the unit as illustrated in Figure 18 Wind Barrier When prevailing wind is...

Page 12: ...rface to avoid ice build up around the unit Place the unit above a load bearing wall or area of the roof that can adequately support the unit Consult local codes for rooftop applications CAUTION Roof...

Page 13: ...ch this system contains While it may have some miscibility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil 7 Align...

Page 14: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cy...

Page 15: ...size Make all electrical power wiring connections at the out door unit Be sure to reattach all electrical box covers after con nections are complete Indoor Unit All indoor units are powered by the out...

Page 16: ...208 230V Indoor Unit Outdoor Unit Indoor Unit Figure 27 Single Zone Wiring 30K and Below From Power Supply Indoor Unit CommunicationTerminal Block L1 L2 Power Terminal Block 208 230V Outdoor Unit L1 L...

Page 17: ...Output Remote Control Ceiling Floor Type CN21 M 5 5 VSWING INACTIVE CN24 M 5 SWING FAN FOR MODE CONFLICT SETTING DISPLAY BOARD 10 CN10A TO WIRED CONTROLLER 2 CN40 TO PRO GRA MMABL E WIR ED CON TRO LLE...

Page 18: ...and regular wired controller use the same wiring connector Figure 31 MCFA036S4 P Unit Wiring Diagram CN5 Inductor CN8 CN18 CN7 T2B OUTER PIPE TEMP SENSOR T2 T1 CN6 4 BLACK WHITE RED RED VSWING INACTI...

Page 19: ...OR TEMP SENSOR POW ER SUPPLY H PRO SV L PFC INDUCTOR COMPRESSOR DISCHARGE TEMP SENSOR RED BLACK V U CN19 CN51 CN55 W EXV BLACK DRIVER BOARD RED 7 7 YELLOW BLUE P 1 FM1 OUTDOOR DC FAN CN53 CN20 CN34 CN...

Page 20: ...N17 CN39 CN18 HEAT_D HEAT_Y SV 4 WAY BLUE BLUE RED BLUE CN4 CN2 CN3 CN1 COMP U V W Y G DCFAN2 DCFAN1 5 5 CN6 CN5 CN8 CN15 CN9 CN14 7 5 CN6 CN3 L YELLOW YELLOW U V W BLUE BLACK RED Y G CN39 WHITE BLACK...

Page 21: ...OARD C ODE PAR T NAME C OMP R E S S OR D HE AT1 C T1 AC CURRENT DETECTOR 4 WAY VALVE C OMP E XV E LE C TR IC E XPANS ION VALVE H P R O L P R O LOW P R E S S UR E S WIT CH HIG H P R E S S UR E S WIT CH...

Page 22: ...RED BLACK V U CN19 CN51 CN55 W EEV BLACK DRIVER BOARD RED YELLOW BLUE P 1 FM1 OUTDOOR DC FAN FAN MOTOR CAPACITOR CN53 CN20 CN3 CN4 CN10 CN40 CN22 CN44 CN8 CN9 CN7 CN2 CN1 CN5 CN54 CN52 CN33 5 6 CN6 SV...

Page 23: ...e Length feet meters Amount of Refrigerant to add 18 25 7 5 0 161 oz ft 15g m 24 25 7 5 0 322 oz ft 30g m 36 25 7 5 0 322 oz ft 30g m 48 25 7 5 0 322 oz ft 30g m Troubleshooting Table 7 Troubleshootin...

Page 24: ...crements NOTE The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over shoot the temperature setting by 6 10 F 3 5 C depending on the room size or...

Reviews: